3 EMC COUNTERMEASURES
3.4 Cable layout
Controller connection (command) cable (except for SSCNET III
cable) (3)
If controller and servo amplifier are in the same cabinet
Use a shielded twisted pair cable, and ground it on both sides of the controller and servo amplifier with P clips or U clips.
When the cable length is 2 m or less, ground the cable on the controller side.
If controller or others is in the different cabinet from servo amplifier
Use a shielded twisted pair cable, and ground it on both sided of the controller or others and servo amplifier with P clips or U
clips.
Cabinet
Shield twisted pair cable
As close as
possible
As close as
possible
Servo
amplifier
Controller
Cabinet
Shield twisted pair cable
Controller, etc.
Cabinet
10 cm or less
10 cm or less
Servo
amplifier