5 FUNCTIONS
5.1 Function List
59
5
RAS function
Diagnostic function
Other functions
Function
Description
Reference
Slave station disconnection
Only the stations where an error has occurred, including slave stations, are
disconnected from the network, and the data link is continued only with the
stations operating normally. In a line topology system, stations after the station
where the error occurred are disconnected.
Automatic return
When a station disconnected from a network due to a data link error recovers
from the error, the station is automatically reconnected to the network and
restarts data link.
Loopback function
This function disconnects only faulty stations, and continues data link with only
normal stations. It also continues data link with normal stations connected
after the faulty station which is disconnected in a line topology.
Function
Description
Reference
CC-Link IE Field Network diagnostics
The status of the CC-Link IE Field Network can be checked by CC IE Field
Utility. The faulty area, cause of the fault and its corrective action, and event
history can be checked.
Page 118 Diagnosing CC-
Link IE Field Network
Individual board
diagnostics
Bus I/F test
Check the hardware related to the bus I/F function of the CC-Link IE Field
Network board.
Memory test
Check the memory of the CC-Link IE Field Network board.
Hardware test
Check the hardware in the CC-Link IE Field Network board.
Self-loopback test
Check the communication circuit of the transmission system of the CC-Link IE
Field Network board.
Own network
diagnostics
Loop test
Check the network circuit status and parameter setting status of each station.
Cable test
Check the connection status of the Ethernet cable.
Other network
diagnostics
Communication test
Check whether the communication path for transient transmission from the
own station to the target station is correct.
Function
Description
Reference
Reserved station specification
The reserved stations are included in the number of stations that will be
connected to the network in the future without actually connecting them.
Reserved stations are not detected as faulty stations even though they are not
actually connected.
Station Specification
and Reserved Station
Function Disable
Function
Reserved station function disable
Reserved stations can be temporarily disabled without changing parameters.
Error invalid station and temporary error invalid
station setting
The master station does not detect a slave station as a faulty station even if
the slave station is disconnected during data link. This can be used when a
slave station is replaced during data link, for instance.
Station and Temporary
Error Invalid Station
Setting Function
Event notification to program
Event conditions are checked every link scan, and if the event conditions are
met, notifies events to the user program.
• Page 77 Event Function
• Page 104 Event setting
Driver WDT function
This function monitors the operation of the software (operating system, driver)
inside the hardware.
Parameter setting function for CC-Link IE Field
Network remote device station
The parameters of CC-Link IE Field Network remote device station can be set
by using mdRemBufWriteEx function or mdRemBufReadEx function of
MELSEC data link library.
MELSEC Data Link
Library Reference Manual
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......