9 INSTALLATION AND WIRING
9.2 Wiring
143
9
Wiring the terminal block for test pulse output
■
Tightening torque
Tighten terminal block mounting screws within the following torque range. If screws are tightened excessively, the module's
case may be damaged.
■
Cable to be used
The following table shows the cable to be connected to the terminal block for test pulse output.
■
Mounting and removing a terminal block
To remove a terminal block, loosen the terminal block mounting screws with a flathead screwdriver, and then pull out the
terminal block.
To mount a terminal block, insert it into the module, and mount it securely with the terminal block mounting screws.
If the terminal block fails to be fixed securely, it may cause drop, short-circuit, or malfunction.
Screw location
Tightening torque range
Terminal block mounting screw (M2.5 screw)
0.2 to 0.3N
m
Wire diameter
Type
Material
Temperature rating
24 to 12 AWG
Stranded wire
Copper wire
75
or more