FX2N-32DP-IF Profibus-DP Interface Unit
Introduction 1
1-3
a) Profibus-DP communication port (D-SUB 9 pin)
b) Power supply terminals (screw terminal: M3.5 (0.14"))
FX
2N
-32DP-IF (AC power supply type): L, N and grounding terminal
FX
2N
-32DP-IF-D (DC power supply type): 24+, 24- and grounding terminal
c) Direct mounting hole (2-
φ
4.5 (0.18"))
d) 24 V DC power terminal (screw terminal: M3.5 (0.14"))
FX
2N
-32DP-IF-D does not have this terminal.
e) RUN/STOP switch: When this switch is in the RUN position, the 32DP-IF will exchange
data with extension units/blocks and special function blocks. If this
switch is in the STOP position, the 32DP-IF will exchange only input
data with extension units/blocks.
f) Communication port for FX-20P-E or personal computer
g) POWER LED:
ON when power is supplied.
h) RUN LED:
ON when 32DP-IF is exchanging data with extension units/blocks
and special function blocks.
i) BF LED:
ON when a communication error is detected (No data exchange).
j) DIA LED:
ON when diagnostic data is detected.
k) Hook for DIN rail mounting
l) DIP switches for slave address of this unit
m) Extension port
n) Groove for DIN rail mounting (DIN rail width: 35 mm (1.38"))
Summary of Contents for MELSEC FX2N-32DP-IF
Page 1: ...HARDWARE MANUAL FX2N 32DP IF Profibus DP Interface Unit ...
Page 4: ...FX2N 32DP IF Profibus DP Interface Unit ii ...
Page 8: ...FX2N 32DP IF Profibus DP Interface Unit vi ...
Page 20: ...FX2N 32DP IF Profibus DP Interface Unit Introduction 1 1 10 MEMO ...
Page 40: ...FX2N 32DP IF Profibus DP Interface Unit Specifications 3 3 4 MEMO ...
Page 46: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 5 5 4 MEMO ...
Page 53: ......