64
Commercial line
P SERIES -
PUZ-ZM
MITSUBISHI ELECTRIC
/ REPLACE TECHNOLOGY - COMMERCIAL
* 1
ZM50: maximum pipe lenght is 10m
* 2
Change the SW8-1 on the outdoor controller circuit board from OFF to ON.
* 3
The maximum lenght is 100 m in case of new pipes.
*
The maximum lenght is 100 m in case of new pipes.
(2) TWIN SYSTEM
(1) MONOSPLIT SYSTEM
*
The maximum lenght is 100 m in case of new pipes.
(3) TRIPLE SYSTEM
Maximum pipe lenght (ZM35-140)
Liquid pipe
(mm)
OD
ø6.35
ø9.52
ø12.7
Thickness
t0.8
t0.8
t0.8
Gas pipe
(mm)
OD
ø9.52
ø12.7
ø15.88
ø12.7
ø15.88
ø19.05
ø15.88
ø19.05
Thickness
t0.8
t0.8
t1.0
t0.8
t1.0
t1.0
t1.0
t1.0
ZM35,50
30m
*1
[30m]
Standard size
50m
[30m]
*2
30m
[30m]
30m
[20m]
*2
30m
[20m]
ZM60,71
10m
[10m]
10m
[10m]
30m
[30m]
Standard size
55m
[30m]
30m
[20m]
ZM100,125,140
Standard size
100m*
3
[30m]
50m
[30m]
50m
[20m]
50m
[20m]
<Table 2> Maximum pipe lenght (ZM71-140)
ZM71(35x2)
ZM100(50x2)
ZM125(60x2) + ZM140(71x2)
Main pipe
(mm) [A]
Liquid pipe
ø6.35
ø9.52
ø9.52
ø9.52
ø12.7
ø9.52
ø9.52
ø12.7
Gas pipe
ø12.7
ø15.88
ø15.88
ø19.05
ø19.05
ø15.88
ø19.05
ø19.05
Branch pipe
(mm) [B, C]
Liquid pipe
ø6.35
Standard size
55m
[30m]
Standard size
100m*
[30m]
50m
[30m]
50m
[20m]
Gas pipe
ø12.7
Liquid pipe
ø9.52
50m
[30m]
50m
[30m]
50m
[30m]
50m
[20m]
Standard size
100m*
[30m]
50m
[30m]
50m
[20m]
Gas pipe
ø15.88
Liquid pipe
ø12.7
Gas pipe
ø19.05
<Table 3> Maximum pipe lenght (ZM140)
ZM140(50x3)
Main pipe
(mm) [A]
Liquid pipe
ø9.52
ø9.52
ø12.7
Gas pipe
ø15.88
ø19.05
ø19.05
Branch pipe
(mm) [B, C, D]
Liquid pipe
ø6.35
Standard size
100m*
[30m]
50m
[30m]
50m
[20m]
Gas pipe
ø12.7
Liquid pipe
ø9.52
50m
[30m]
50m
[30m]
50m
[20m]
Gas pipe
ø15.88
Liquid pipe
ø12.7
Gas pipe
ø19.05
Marks in the table
: It can be used.
: Cooling capacity is lowered.
: Additional refrigerant charge is required when the pipe lenght
exceeds 20 m.
50m
[30m]
The maximum pipe lenght.
Charge-less pipe lenght.
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......