17
MITSUBISHI ELECTRIC
/ MXZ SERIES
MXZ-F
MXZ SERIES - MULTI SPLIT -
DC Inverter/Heat Pump - 2 to 6 ports
SIZE
DIAMETER
EXTERNAL PIPING
REFRIGERANT CHARGE
ELECTRICAL DATA
Liquid mm
(inches)
Gas mm
(inches)
Max
Height
Max
Length
Max Pipe
Bends
Pre-charge
Kg
Pre-charge
lenght mt.
Additional
charge
g/mt
tonCO
2
eq
max charge
Operating
current max
Breaker
MXZ-2F33VF2(3)
TAB.
10
15/20
15/20
1
20
-
0,68
10,00
15 A
MXZ-2F42VF2(3)
15
20/30
20/30
1,2
30
-
0,81
12,20
15 A
MXZ-2F53VF2(3)
15
20/30
20/30
1,2
30
-
0,81
18,00
15 A
MXZ-2F53VFHZ
15
20/30
20/30
2,4
30
-
1,62
18,00
16 A
MXZ-3F54VF
15
25/50
25/50
1,4
TAB.
0,95
18,00
25 A
MXZ-3F68VF
15
25/60
25/60
1,4
0,95
18,00
25 A
MXZ-4F72VF
15
25/60
25/60
1,4
0,95
18,00
25 A
MXZ-3F54VF2(3)
15
25/50
25/50
2,4
50
-
1,62
18,00
25 A
MXZ-3F68VF2(3)
15
25/60
25/60
2,4
60
-
1,62
18,00
25 A
MXZ-4F72VF2(3)
15
25/60
25/60
2,4
60
-
1,62
18,00
25 A
MXZ-4F80VF2(3)
15
25/60
25/60
2,4
60
-
1,62
18,00
25 A
MXZ-4F83VFHZ
15
25/70
25/70
2,4
70
-
1,62
21,4
30 A
MXZ-4F83VF
15
25/60
25/70
2,4
70
-
1,62
21,4
25 A
MXZ-5F102VF
15
25/80
25/80
2,4
80
-
1,62
21,4
25 A
MXZ-6F122VF
15
25/80
25/80
2,4
80
-
1,62
29,8
32 A
MIN AREA according to standard CEI EN 60335-2-40 ED6 R32 - HUMAN COMFORT
UNIT
2F33 VF(2)
2F42/2F53 VF(2)
2F33 VF3
2F42/2F53 VF3
2F53_VFHZ/3F54/3F68
4F72/4F80
4F83 VF/VFHZ
5F102/6F122
Indoor Type
Max
charge
(kg)
Min Area
(m²)
Max
charge
(kg)
Min Area
(m²)
Max
charge
(kg)
Min Area
(m²)
Max
charge
(kg)
Min Area
(m²)
Max
charge
(kg)
Min Area
(m²)
Max
charge
(kg)
Min Area
(m²)
Max
charge
(kg)
Min Area
(m²)
Max
charge
(kg)
Min Area
(m²)
WALL MOUNTED
1
no
limitation
1,20
no
limitation
0,8
no
limitation
1,00
no
limitation
2,40
5,45
2,40
5,45
2,40
5,45
2,40
5,45
FLOOR STANDING
1
no
limitation*
1,20
no
limitation*
0,8
no
limitation*
1,00
no
limitation*
2,40
4,74*
2,40
4,74*
2,40
4,74*
2,40
4,74*
CEILING - DUCTED
1
no
limitation
1,20
no
limitation
0,8
no
limitation
1,00
no
limitation
2,40
3,65
2,40
3,65
2,40
3,65
2,40
3,65
L
N
230V
Breaker
MXZ-F_VF(2/3)
UNIT A
UNIT C
UNIT B
UNIT D
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
* Leakage sensor
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......