114
Rotation and Back-up
Setting No.
(Request code)
Setting contents
Initial
settings
No.1 (310)
Monitoring the request code of current setting
No.2 (311)
Rotation and Back-up OFF
(Normal group control operation)
No.3 (312)
Back-up function only
No.4 (313)
Rotation ON
(Alternating interval = 1day) and back-up function
No.5 (314)
Rotation ON
(Alternating interval = 3days) and back-up function
No.6 (315)
Rotation ON
(Alternating interval = 5days) and back-up function
No.7 (316)
Rotation ON
(Alternating interval = 7days) and back-up function
No.8 (317)
Rotation ON
(Alternating interval = 14days) and back-up function
No.9 (318)
Rotation ON
(Alternating interval = 21days) and back-up function
2nd Stage
Setting No.
(Request code)
Setting contents
Initial
settings
No.1 (320)
Monitoring the request code of current setting
No.2 (321)
Cut-in function OFF
No.3 (322)
Cut-in function ON (Set point = Set temp.+ 4: [7.2°F]
No.4 (323)
Cut-in function ON (Set point = Set temp.+ 6: [10.8°F]
No.5 (324)
Cut-in function ON (Set point = Set temp.+ 8: [14.4°F]
Special functions PAR-40MAA / PAR-21MAA
Rotation, Back-Up e 2nd stage
Outdoor unit 1
Indoor unit 1
Outdoor unit 2
Indoor unit 2
PAR40MAA
SETTING OF OUTDOOR UNIT REFRIGERANT ADDRESS
Main and sub units should be set using Dip-Switch SW1 (da
3 a 6) on the outdoor unit PC board (standard set is Off). Set
refrigerant address as follow:
Main
unit
3/2
3/2
Sub
unit
Refrigerant
address
00
Refrigerant
address
01
OC-1
IC-1
OC-2
IC-2
LEGENDA
OC = Outdoor unit
IC =
RC = Remote
controller
Refrigerant address SW1 have to be setted on
the outdoor unit
Refrigerant address 00
Refrigerant address 01
OC-1
1
2
3
4
5
6
ON
OC-2
1
2
3
4
5
6
ON
SW1
SW1
Setting mode for functions: ROTATION, BACK-UP E SET UP 2nd Stage
A CONTROL
- MR.SLIM - ROTATION E BACKUP
MITSUBISHI ELECTRIC
/ FUNCTION AND SETTINGS
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......