22
MITSUBISHI ELECTRIC
/ MXZ SERIES
MXZ-D/E
MXZ SERIES - MULTI SPLIT -
DC Inverter/Heat Pump - 2 to 6 ports
SIZE
DIAMETER
EXTERNAL PIPING
REFRIGERANT CHARGE
BREAKER
Liquid mm
(inches)
Gas mm
(inches)
Max
Height
Max
Lenght
Max
Pipe Bends
Precharge
Kg
Precharge
lenght
mt.
Additional
charge
g/mt
tonCO
2
eq
precharge
tonCO
2
eq
max charge
MXZ-2D33VA
TAB.
10
15/20
15/20
1,15
20
20
0,78
0,78
15 A
MXZ-2D42VA
15
20/30
20/30
1,30
20
0,88
1,01
15 A
MXZ-2D53VA
15
20/30
20/30
1,30
20
0,88
1,01
15 A
MXZ-3E54VA
15
25/50
25/50
2,70
40
1,82
1,96
25 A
MXZ-3E68VA
15
25/60
25/60
2,70
40
1,82
2,09
25 A
MXZ-4E72VA
15
25/60
25/60
2,70
40
1,82
2,09
25 A
MXZ-4E83VA
15
25/70
25/70
2,99
25
2,02
2,63
25 A
MXZ-5E102VA
15
25/80
25/80
2,99
0
2,02
3,10
25 A
MXZ-6D122VA2
15
25/80
25/80
4,00
30
2,70
3,38
25 A
R410A
L
N
230V
Breaker
MXZ-D/E_VA2
UNIT A
UNIT C
UNIT B
UNIT D
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Example of total additional charge calculation
Formula
∆W(g) = [Lenght of pipes (m) -
Precharge lenght (m)] x additional charge (g/m)
Example
Outdoor unit
= MXZ-3E68VA
Total pipes lenght
(inlet piping only) = 45 m
Lenght with additional charge
(as tab) = 40 m
Additional charge = 20 g/m
Calculation: ∆W(g) = [45 - 40] x 20 = 100 g
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......