U-78
CHAPTER 8
•
Filters
4. Comparing Dust Collection Efficiency Measurement
Methods
The gravitational, colorimetric, and counting methods used for measuring dust collection efficiency each have different features
and must be used according to filter application.
Test Method
Test Dust
Inward Flow Dust
Measurement Method
Outward Flow Dust
Measurement Method
Efficiency
Indication Method
Type of Applicable
Filters
AFI
Gravitational
method
Synthetic:
• Dust on standard
road in Arizona: 72%
• K-1 carbon black: 25%
• No. 7 cotton lint: 3%
Dust weight
measured
beforehand
• Filter passage air
volume measured
• Weigh the dust
remaining on the
filter and compare
Gravitational ratio
Synthetic dust filters
NBS
Colorimetric
method
Atmospheric dust
Degree of
contamination of
white filter paper
Degree of
contamination of
white filter paper
Comparison of
contamination of
reduction in degree
of contamination
Electrostatic dust
percentage of
(for air conditioning)
DOP
Counting
method
Diameter of dioctyl-
phthalate small drop
particles: 0.01mil (0.3 µm)
Electrical counting
measurement using
light aimed at DOP
Same as left
Counting ratio
Absolute filter and
same type of high
efficiency filter
ASHRAE
Gravitational
method
Synthetic:
• Regulated air cleaner
fine particles: 72%
• Morocco Black: 23%
• Cotton linter: 5%
Dust weight
measured
beforehand
• Filter passage air
volume measured
• Weigh the dust
remaining on the
filter and compare
Gravitational ratio
Pre-filter
Filter for air
conditioning
(for coarse dust)
ASHRAE
Colorimetric
method
Atmospheric dust
Degree of
contamination of
white filter paper
Degree of
contamination of
white filter paper
Comparison of
percentage of
reduction in degree
of contamination
Filter for air
conditioning (for fine
dust) Electrostatic
dust collector
Air filter test for air
conditioning set by
Japan Air Cleaning
Assoc.
(Colorimetric test)
JIS 11-type dust
Degree of
contamination of
white filter paper
Degree of
contamination of
white filter paper
Comparison of
percentage of
reduction in degree
of contamination
Filter for air
conditioning
Pre-filter test set
by Japan Air
Cleaning Assoc.
(Gravitational
test)
JIS 8-type dust
Dust weight
measured
beforehand.
• Filter passage air
volume measured
• Weigh the dust
remaining on the
filter and compare.
Gravitational ratio
Pre-filter
Electrostatic air
cleaning device test
set by Japan Air
Cleaning Assoc.
(Colorimetric test)
JIS 11-type dust
Degree of
contamination of
white filter paper
Degree of
contamination of
white filter paper
Comparison of
percentage of
reduction in degree
of contamination
Electrostatic dust
collector
Summary of Contents for Lossnay LGH-F1200RX5-E
Page 2: ...Y11 001 Jun 2012 MEE ...
Page 7: ......
Page 8: ...Lossnay Unit ...
Page 9: ......
Page 10: ...CHAPTER 1 Ventilation for Healthy Living ...
Page 23: ......
Page 24: ...CHAPTER 2 Lossnay Construction and Technology ...
Page 30: ...CHAPTER 3 General Technical Considerations ...
Page 45: ......
Page 46: ...U 37 CHAPTER 4 Characteristics CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 67: ......
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 79: ......
Page 80: ...CHAPTER 7 Installation Considerations ...
Page 83: ......
Page 84: ...CHAPTER 8 Filters ...
Page 90: ...CHAPTER 9 Service Life and Maintenance ...
Page 93: ......
Page 94: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 99: ......
Page 100: ...CHAPTER 11 Lossnay Q and A ...