U-6
CHAPTER 1
•
Ventilation for Healthy Living
Comparing Centralized Ventilation and Independent Zoned Ventilation Methods
Centralized Ventilation Method
Independent Zoned Ventilation Method
S
yst
em Fle
xibilit
y
Fan Power
The air transfer distance is long, thus requiring
much fan power.
As the air transfer distance is short, the fan power is
small.
Installation Area
• Independent equipment room is required.
• Duct space is required.
• Penetration of floors with vertical shaft is not
recommended in terms of fire prevention.
• Independent equipment room is not required.
• Piping space is required only above the ceiling.
Zoning
Generalized per system.
Can be used for any one area.
Design
• Design of outer wall is not lost.
• The indoor supply air diffuser and return grille can
be selected without restrictions for an appropriate
design.
• The number of intakes and exhaust air outlets on
an outside wall will increase; design must be
considered.
• The design will be fixed due to installation fittings,
so the design of the intakes and exhaust air
outlets must be considered.
Control
• As the usage set time and ventilation volume
control, etc., are performed in a central monitoring
room, the user’s needs may not be met
appropriately.
• A large amount of ventilation is required even for
a few occupants.
• The user in each zone can operate the ventilator
without restrictions.
• The ventilator can be operated even during off-
peak hours.
Comfort
• An ideal supply air diffuser and return grille
position can be selected as the supply air diffuser
and return grille can be positioned without
restrictions.
• The only noise in the room is the sound of air movement.
• Antivibration measures must be taken as the fan in
the equipment room is large.
• Consideration must be made because of the
noise from the main unit.
• Antivibration measures are often not required as
the unit is compact and any generated vibration
can be dispersed.
S
yst
em Management
Maintenance and
Management
• Centralized management is easy as it can be
performed in the equipment room.
• The equipment can be inspected at any time.
• Work efficiency is poor because the equipment is
not centrally located.
• An individual unit can be inspected only when the
room it serves is vacant.
Trouble influence
• The entire system is affected.
• Immediate inspection can be performed in the
equipment room.
• Limited as only independent units are affected.
• Consultation with the tenant is required prior to
inspection of an individual unit.
Costs
Because there are many common-use areas, if the
building is a tenant building, an accurate
assessment of operating cost is difficult.
Invoicing for each zone separately is possible, even
in a tenant building.
Summary of Contents for Lossnay LGH-F1200RX5-E
Page 2: ...Y11 001 Jun 2012 MEE ...
Page 7: ......
Page 8: ...Lossnay Unit ...
Page 9: ......
Page 10: ...CHAPTER 1 Ventilation for Healthy Living ...
Page 23: ......
Page 24: ...CHAPTER 2 Lossnay Construction and Technology ...
Page 30: ...CHAPTER 3 General Technical Considerations ...
Page 45: ......
Page 46: ...U 37 CHAPTER 4 Characteristics CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 67: ......
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 79: ......
Page 80: ...CHAPTER 7 Installation Considerations ...
Page 83: ......
Page 84: ...CHAPTER 8 Filters ...
Page 90: ...CHAPTER 9 Service Life and Maintenance ...
Page 93: ......
Page 94: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 99: ......
Page 100: ...CHAPTER 11 Lossnay Q and A ...