Lossnay Q and A
Question
Answer
Remarks
8
Can Lossnay units be used
for hospital air conditioning?
According to the results from a test performed by the Tokyo University
Hospital (Inspection Center, Prof. Kihachiro Shimizu), as the supply air and
exhaust air pass through different passages, bacteria transmission from
exhaust side to supply side is low. They found:
1) Bacteria do not propagate in the Lossnay Core.
2) Even if bacteria accumulated in the Lossnay unit, it died off in
approximately two weeks.
9
Because entry into the
Lossnay Core is small,
won’t it clog easily?
Normally the original state of the filter can be regained by cleaning it with a
vacuum more than once every year, and the two intake side surfaces of the
Lossnay Core more than once every two years. Dust will not accumulate in
the passage due to the laminar flow if the air is normal.
“Normal air” refers to
air that does not
contain oil mist, etc.
When exhausting air
contains oil mist, etc.,
install a filter at return
grille.
10
What is the air leakage
rate?
This will be different depending on the position of the fans, but for “both
suction” or “both forced”, the rate is 2% to 3%. LGH type fan position is “both
forced”.
For using LU type, if the difference in static pressure between SA and RA,
and EA and OA is 2.0 inH
2
O, the air leakage rate will be 2.5% and 3.4%
respectively. This value is not a problem for actual use.
However, the single suction or single forced methods will have a leakage rate
of 10% or higher and should be avoided.
11
Can Lossnay units be
used in extreme cold
climates (14°F(-10°C) or
lower)?
If the winter room air temperature is above 68°F (20°C), humidity is above
50%, and the outdoor temperature is 14°F (-10°C) or lower, moisture
condensation or frost will develop on the Lossnay Core. In this case, the
intake air must be preheated.
Plot the Lossnay intake side air conditions A and B on a psychrometric chart as
shown below. If the high temperature side air B intersects the saturation curve
such as at C, moisture condensation or frost will accumulate on the Lossnay
unit. In this case, the air should be warmed up to the temperature indicated by
Point A’ so that Point C reaches the C’ point.
A
A’
C
B
C’
Lossnay
EA
OA
RA
SA
Lossnay
EA
OA
RA
SA
Turbulent flow
Laminar floe
Outdoor
Exhaust fan
Indoor
Supply fan
Exhaust fan
Supply fan
Outdoor Indoor
Dry bulb temperature (°F (°C))
Absolut
e humidit
y (Ib/Ib’
(k
g/k
g’))
Saturation curve
Summary of Contents for Lossnay LGH-F1200RX5-E
Page 2: ...Y11 001 Jun 2012 MEE ...
Page 7: ......
Page 8: ...Lossnay Unit ...
Page 9: ......
Page 10: ...CHAPTER 1 Ventilation for Healthy Living ...
Page 23: ......
Page 24: ...CHAPTER 2 Lossnay Construction and Technology ...
Page 30: ...CHAPTER 3 General Technical Considerations ...
Page 45: ......
Page 46: ...U 37 CHAPTER 4 Characteristics CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 67: ......
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 79: ......
Page 80: ...CHAPTER 7 Installation Considerations ...
Page 83: ......
Page 84: ...CHAPTER 8 Filters ...
Page 90: ...CHAPTER 9 Service Life and Maintenance ...
Page 93: ......
Page 94: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 99: ......
Page 100: ...CHAPTER 11 Lossnay Q and A ...