Definition of Symbols

M1:

Motor for exhaust fan

CN1:

Connector (Transformer primary)

M2:

Motor for supply fan

CN2:

Connector (Transformer secondary)

C:

Capacitor

CN5:

Connector (Thermistor)

GM:

Motor for By-pass operation

CN6:

Connector (Microswitch)

LS:

Microswitch

CN7:

Connector (Motor for By-pass operation)

TH1:

Thermistor for outside air

TAB3:

Tab connector(Fan motor)

TH2:

Thermistor for return air

TAB5:

Tab connector (Fan motor)

SW1:

Switch (Main/Sub change)

CN9:

Connector (Fan motor)

SW2, 5:

Switch (Function selection)

CN10:

Connector (Fan motor)

TM1:

Terminal block (Power supply)

CN16:

Connector (High/Low/By-pass switch)

TM2:

Terminal block (External control input)

CN32:

Connector (Remote control selection)

TM3:

Terminal block (Monitor output)

SA1:

Address setting rotary switch (10 digit)

TM4 :

Terminal block (Transmission cable and monitor output)

SA2:

Address setting rotary switch (1 digit)

TB5 :

Terminal block (M-NET Transmission cable)

SYMBOL

: Indicates terminal block.

TAB1,TAB2:

Connector(Power supply)

: Connector.

TR1:

Control circuit transformer

: Board insertion connector or fastening

X10,X11,X12:

Relay contact

connector of control board.

Wiring Diagrams

LGH-15RX

5

to 100RX

5

BLACK

BLACK

LS

LS

BLACK

BLACK

RED

WHITE

TR3

RED

WHITE

TR2

x201

x202

x203

x101

x102

x103

M

M

M

1

2

1

M

2

EXHAUST

SUPPLY

EXHAUST

FAN MOTOR

FAN MOTOR

FAN MOTOR

SUPPLY
FAN MOTOR

C

C

C

C

cable

transmission

M-NET

MELANS

(non-polar)

Mr.Slim

output  7 , 8

Malfunction monitor

monitor output  6 , 7

By-pass or Delay2 

Sheild Wire

12V or 24V   DC

BROWN
RED

TM4

CN16

10

8

7

6

1

2

3

CN5

1

2

9

A

B

S

X10

CN32

X11

X12

Isolator

TAB2

TAB1

CN9

CN10

TAB5

TAB3

TM3

TB5

Transmission
cable

60DR-E

PZ-

BROWN

TM2

ORANGE

ORANGE

ORANGE

ORANGE

TH2(RA)

TH1(OA)

SW1

SW5

SW2

SA1 SA2

BLACK
GREY
YELLOW

ORANGE

WHITE

BLUE

BLUE

RED

BROWN

BROWN

BLUE

CN7

CN2

CN1

TM1

monitor output

Operation or Delay1

PE

N

N

L

L

     24VDC   2A           5VDC     100mA

MAX 240VAC 2A   MIN 220VAC 100mA

(non-polar)

TR1

BROWN
BLACK

GREY
YELLOW

YELLOW

GREY

BLACK

BROWN

WHITE

BLUE

ORANGE

RED

RED
ORANGE
BLUE
WHITE

3

1

Unchanged a-conntact

External control input

A

2nd or later main units

cable

transmission

M-NET

S

B

TB5(M-NET)

Sheild Wire

TM4

(PZ-60DR-E)

2nd remote controller

installable)

(*1)
Optional Remote controller

(Max.2 remote controllers

PZ-41SLB-E and PZ-52SF-E cannot 

be used when using PZ-60DR-E 

(*1)

      5VDC     100mA

MIN 220VAC 100mA

     24VDC   1A

MAX 240VAC 1A

    transmission wire to      ,       on TB5 terminal

B

A

2

1

          of TM4 terminal block,and connect M-NET

    is used as the M-NET System ,connect it to 

    block.

  *When the optional Remote Controller PZ-60DR-E

GM MG

GM MG

x103

x102

x101

x203

x202

x201

2

1

GREEN/YELLOW

POWER SUPPLY
220-240V   50Hz 

CN16
(Unchanged a-conntact)

RED

BROWN

YELLOW

ORANGE

GREEN

HI

LO

BY-PASS

With this product, the wiring installation method will 
vary according to the design of the system.  
Perform electrical installation to meet local electrical regulations.   
 .Always use double insulated PVC cable for the transmission cables.  
 .Wiring work must be performed by qualified professionals.  
 .All supply circuits must be disconnected before obtaining access to the terminal devices.  

NOTE  1.TM1, TM2, TM3, TM4, TB5 shown 
               in dotted lines are field work.
            2.Isolator should be provided by the customer.
            3.Be sure to connect the grounding wire.

*Attention

M

C

C

(*2) LGH-200RX

5

 has 2 

       capacitors per mortor 
       as following drawing.

(*2)

(*2)

(*2)

(*2)

2nd remote controller

(Max.2remote controllers installable cable)

2nd LOSSNAY unit (Up to max 15 units)

(*1)

LGH-150RX

5

and 200RX

5

Definition of Symbols

M1:

Motor for exhaust fan

X10,X11,X12: Relay contact

M2:

Motor for supply fan

X101,X102,X103: Relay Supply fan speed control

C:

Capacitor

X201,X202,X203: Relay Exhaust fan speed control

GM:

Motor for By-pass operation

CN1:

Connector (Transformer primary)

LS:

Microswitch

CN2:

Connector (Transformer secondary)

TH1:

Thermistor for outside air

CN5:

Connector (Thermistor)

TH2:

Thermistor for return air

CN6:

Connector(Microswitch)

SW1:

Switch (Main/Sub change)

CN7:

Connector (Motor for By-pass operation)

SW2, 5:

Switch (Function selection)

CN9:

Connector (Fan motor)

TM1:

Terminal block (Power supply)

TAB3:

Tab connector (Fan motor)

TM2:

Terminal block(External control input)

TAB5:

Tab connector (Fan motor)

TM3:

Terminal block (Monitor output)

CN9:

Connector (Fan motor)

TM4:

Terminal block

CN10:

Connector (Fan motor)

(Transmission cable and monitor output)

CN16:

Connector(High/Low/By-pass switch)

TB5:

Terminal block (M-NET Transmission cable)

CN32:

Connector (Remote control selection)

TAB1,TAB2: Connector(Power supply)

SA1:

Address setting rotary switch (10 digit)

TR1:

Control circuit transformer

SA2:

Address setting rotary switch (1 digit)

TR2,TR3:

By-pass operation transformer

SYMBOL

: Indicates terminal block.

Board insertion connector or fastening
connector of control board.

*Specifications may be subject to change without notice.

*Specifications may be subject to change without notice.

POWER SUPPLY

220-240V   50Hz 

2

1

TB5(M-NET)

(*1)

Optional Remote controller

A

B

S

(PZ-60DR-E)

*When the optional Remote Controller PZ-60DR-E

cable
(non-polar)

     24VDC   2A            5VDC     100mA 

MAX 240VAC 2A    MIN 220VAC 100mA 

L

L

N

N

M

1

M

2

PE

monitor output

Operation or Delay1

LS

TR

TM1

CN1

CN2

CN7

BLUE

BROWN

YELLOW

RED

BROWN

RED

BLUE

BLUE

EXHAUST
FAN MOTOR

SUPPLY
FAN MOTOR

WHITE

ORANGE

YELLOW

GREY

BLACK

C

C

SA2

SA1

SW2

SW5

SW1

CN6

ORANGE

ORANGE

TH1(OA)

TH2(RA)

ORANGE
ORANGE
ORANGE
ORANGE

TM2

BROWN

PZ-
60DR-E

Transmission

TB5

TM3

TAB3

TAB5

CN10

CN9

TAB1

TAB2

Isolator

X12 X11

CN32

X10

S

B

A

9

2

1

CN5

3

2

1

6

7

8

10

CN16

TM4

RED

GREEN/YELLOW

BROWN

output  7 , 8

Malfunction monitor

monitor output  6 , 7

By-pass or Delay2 

MAX 240VAC 1A

12V or 24V   DC

Mr.Slim

(non-polar)

2nd remote controller

(Max.2remote controllers installable cable)

2nd LOSSNAY unit (Up to max 15 units)

MELANS cable

transmission

M-NET

Sheild Wire

     24VDC   1A

MAX 240VAC 1A

      5VDC     100mA 

MIN 220VAC 100mA 

Unchanged a-conntact

1

3

External control input

TM4

(Max.2 remote controllers

2nd remote controller

Sheild Wire

cable

transmission

M-NET

2nd or later main units

installable)

(*1)PZ-41SLB-E and PZ-52SF-E cannot 

be used when using PZ-60DR-E 

    is used as the M-NET System ,connect it to 
         of TM4 terminal block,and connect M-NET
    transmission wire to       ,     on TB5 terminal
    block.

1

2

A

B

GM

CN16

(Unchanged a-conntact)

HI

LO

EXTRA-LO

BY-PASS

M

C

C

(*2) LGH-100RX

5

 has 2 

       capacitors per mortor 
       as following drawing.

(*2)

(*2)

(*1)

With this product, the wiring installation method will 
vary according to the design of the system.  
Perform electrical installation to meet local electrical regulations.   
 .Always use double insulated PVC cable for the transmission cables.  
 .Wiring work must be performed by qualified professionals.  
 .All supply circuits must be disconnected before obtaining access to the terminal devices.  

NOTE  1.TM1, TM2, TM3, TM4, TB5 shown 
               in dotted lines are field work.
            2.Isolator should be provided by the customer.
            3.Be sure to connect the grounding wire.

*Attention

BROWN

RED

ORANGE

YELLOW

GREEN

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...U TOKYO 100 8310 JAPAN http Global MitsubishiElectric com Y08 003 Nov 2008 MEE Specifications subject to change without notice C o n c e n t r a t i n g w h a t w e c a n d o m o r e e v e r a n d d e f i n i t e l y ENERGY RECOVERY VENTILATORS RX5 SERIES MODEL ...

Page 2: ...50 38 5kJ kg DA 33ºC 20 1g kg DA 63 84 6kJ kg DA 26ºC 10 5g kg DA 50 52 9kJ kg DA Energy recovery calculating equation Indoor supply air temperature ºC Indoor temperature ºC Outdoor temperature ºC _ Temp recovery efficiency Outdoor temperature ºC Calculation example 16ºC 20ºC _ 0ºC 80 0ºC Energy recovery calculating equation Indoor supply air temperature ºC Outdoor temperature ºC Indoor temperatur...

Page 3: ...uilding during the cooling season such as early morning or at night By pass ventilation will draw in the cooler outside air and reduce the cooling load on the system 2 Night purge By pass ventilation can be used to release hot air from inside the building that has accumulated in buildings a business district during the hot summer season 3 Office equipment room cooling During cold season fresh air ...

Page 4: ...er than the room temperature ventilation starts automatically The air conditioning load required to reach the set temperature the next morning is reduced At night the outside temperature drops When the room becomes sufficiently cool ventilation is stopped Hot air is discharged Example B Weekly Example A Hourly 8 00 9 00 12 00 13 00 17 00 19 00 22 00 low high low high low extra low new RX5 series w...

Page 5: ... units and general equipment To operate general equipment PAC YG66DCA is required Switches between Cool Dry Auto Fan Heat Group of LOSSNAY unit automatic ventilation vent heat interchange normal ventilation depending on the air conditioner unit Auto mode is for City Multi R2 and WR2 series only Cool Dry 19 67 30 87 14 57 30 87 Heat 17 63 28 83 17 63 28 83 Auto 19 67 28 83 17 63 28 83 in case of us...

Page 6: ...olyolefin EU F7 Standard filter High efficiency filter EA OA Lighting etc Replacement components for the standard air filter supplied with the LOSSNAY LGH main unit Model Applicable model PZ 25RF8 E PZ 35RF8 E PZ 50RF8 E PZ 65RF8 E PZ 80RF8 E PZ 100RF8 E LGH 15RX5 E LGH 25RX5 E LGH 35RX5 E LGH 50RX5 E LGH 65RX5 E LGH 80RX5 E LGH 150RX5 E 2sets LGH 100RX5 E LGH 200RX5 E 2sets Filter material Dimens...

Page 7: ... back for more Cleanliness is the key to an attractive atmos phere and restaurants devote significant effort to ensuring the premises are sanitary Sanitation and cleanliness how ever are not enough No matter how clean a restaurant may look if there are bothersome odors lingering in the air all those efforts go to waste and the restaurant s clean image is tarnished For these reasons we invite resta...

Page 8: ...a high Air volume L s O mmH 2 0 30 25 20 15 10 5 Pa m2 h 300 250 50 100 150 200 250 200 150 100 50 0 20m 10m 5m 15m 50Hz Single phase 240V Exchange efficiency External static pressure 50 60 70 80 90 100mm length dia pipe 10 20 30 40 50 60 70 0 High Unit mm LGH 15 to 100RX5 LGH 150 and 200RX5 LGH 15RX5 E Frequency Power source Ventilation mode Fan speed Current A Power consumption W Air volume Mode...

Page 9: ...where duct direction 63 63 65 65 Inspection opening Extra low Extra high Low Temperature exchange efficiency efficiency Cooling Enthalpy exchange efficiency Heating Enthalpy exchange 25 20 0 150 90 80 70 60 50 Exchange efficiency 50Hz Single phase 240V 30m 20m 10m External static pressure 5 10 15 Pa O 2 H m m 100 90 80 70 60 40 50 Air volume L s m2 h length pipe 40m dia 400 50 100 30 150 200 250 3...

Page 10: ...ore air filter High Position where duct direction Inspection opening 208 192 Extra low Temperature exchange efficiency Enthalpyexchange efficiency Heating Enthalpy exchange efficiency Cooling Extra high Low High Unit mm LGH 50RX5 E LGH 65RX5 E Ventilation mode Fan speed Current A Power consumption W Air volume Model External static pressure Temperature exchange efficiency Enthalpy exchange efficie...

Page 11: ...pection opening 258 242 Low efficiency Heating Enthalpy Temperature exchange efficiency Enthalpy exchange efficiency Cooling exchange Extra high Extra low High 50Hz Single phase 240V External static pressure m 2 H m O 10 20 Exchange efficiency 0 m2 h 350 50 100 150 200 250 300 250mm length pipe dia 50 60 70 80 90 Pa 40 30 50 0 500 100 200 300 400 1200 1000 800 600 400 200 0 100m 60m 20m 40m 80m Ai...

Page 12: ...se 240V Pa Enthalpy exchange efficiency Cooling efficiency Heating Enthalpy exchange Temperature exchange efficiency Low High Extra high 90 80 70 60 50 External static pressure Exchange efficiency 0 500 1000 1500 2000 2500 300 200 100 400 500 m2 h 0 700 600 500 400 300 200 100 Air volume L s 10 20 30 40 50 0 2 H m m O Unit mm LGH 150RX5 E LGH 200RX5 E Ventilation mode Fan speed Current A Power con...

Page 13: ... controller Max 2remote controllers installable cable 2nd LOSSNAY unit Up to max 15 units 1 LGH 150RX5 and 200RX5 Definition of Symbols M1 Motor for exhaust fan X10 X11 X12 Relay contact M2 Motor for supply fan X101 X102 X103 Relay Supply fan speed control C Capacitor X201 X202 X203 Relay Exhaust fan speed control GM Motor for By pass operation CN1 Connector Transformer primary LS Microswitch CN2 ...

Page 14: ...nt condensation from forming If it is expected that the ambient temperature around the place where the LOSSNAY unit is installed will be high during the summer air conditioning season it is recommended that the indoor ductwork be covered with insulation material 7 Inspection opening 450 450 or 600 600mm must be installed on the filter and LOSSNAY core removing side LOSSNAY model selection advices ...

Reviews: