Sample Installations

•Always leave inspection holes (   450 or    600) on the air filter and 
 LOSSNAY core removal side.
• Always insulate the two ducts outside the room (intake air and exhaust 
 air ducts) to prevent condensation.
•It is possible to change the direction of the outside air ducts
  (OA and EA side).
• Do not install the vent cap or round hood where it will come into 
 direct contact with rain water.

•Always leave inspection holes (   450 or    600) on the air filter and 
 LOSSNAY core removal side.
• Always insulate the two ducts outside the room (intake air and exhaust 
 air ducts) to prevent condensation.
•If necessary, order a weather cover to prevent rain water from direct 
 contact or entering the unit.

LGH-150RX

5

LGH-200RX

5

A

1010

1010

B

1045

1272

Unit: mm

A

OA

(Outside air)

EA

(Exhaust air)

OA (Outside air)

EA (Exhaust air)

414

414

Suspension bolt position

Suspension bolt position

Suspension bolt 
position

Exhaust air grille

B

Supply air grille

600 or more

150 to 250

Inspection 

opening

Duct downward slope 1/30 
or more (to wall side)

Deep-type hood or 
weather cover

Duct diameter   200 
(ordered by customer)

Inspection opening

Supply/
exhaust air grille

Suspension bolt position 
(ordered by customer)

RA

(Return air)

SA 
(Supply air)

LOSSNAY core/
air filter/
fan maintenance 
space

(Rainwater entrance 
prevention)

Duct

Duct

Duct diameter   250
(user supplied)

Duct
diameter   200
(user supplied)

(user supplied)

Exhaust grille
(user supplied)

(user supplied)

(user supplied)

(user supplied)

Ceiling suspension
bolt

450(   600) Inspection port

(user 

supplied)

Y piping,Dwindle pipe

Ceiling suspension
bolt position

Ceiling

suspension
bolt position

Exhaust grille

Ceiling
suspension
bolt position

SA

(supply air)

RA

(return air)

OA

(fresh-air intake)

EA

(exhaust-air outlet)

OA

(fresh-air intake)

EA

(exhaust-air outlet)

Heat exchanger/filter
maintenance space

Min. 600

150

~250

B

A

SA

(supply air)

Air-supply grille

Exhaust grille

RA

(return air)

Duct incline
Over 1/30
(toward the wall)
to prevent entry 
of rainwater

Air-supply grille
(user supplied)

(user supplied)

Air-supply grille

Air-supply grille

  450(   600)

Inspection port

(user supplied)

(user supplied)

Model

LGH-15RX

5

to 100RX

5

LGH-150RX

5

and 200RX

5

Attention for specifications

1.Cold operation mode(*1) is to start repeating in the case that LOSSNAY's detected OA temperature is less than-10

°

C. 

*1.Supply air(SA) in the operation for 60min. followed by stop operation for 10min.

2.The current, power consumption and efficiency are based on the air flow rate in the specification.
3.Fan speed is selectable by the remote controller from High (Extra-High), Low, Extra-Low(Extra-Low not equipped LGH-

150RX

5

and 200RX

5

).

Multi Ventilation Mode should set on LOSSNAY unit or remote controller (PZ-60DR-E).

4.LOSSNAY ventilation mode is to start automatically in the case that LOSSNAY's detected OA temperature is less than

+8

°

C,even if By-pass ventilation is set by remote controller.

Remote controller continue to show "By-pass ventilation" in this case.

5.Temperature Exchange efficiency(%) are based on winter condition.
6.Mitsubishi Electric measures the machine according to the Japan Industrial Standards(JIS B 8628)

Attention

1.When using the product where it is exposed to high temperatures and humidity (40

°

C or higher, RH 80% or higher), or

where fog occurs frequently, moisture is likely to condense in the core, and may result in condensation build up in the
unit.The product should not be used under such conditions.

2.Outdoor air may enter the LOSSNAY owing to the pressure difference between indoor and outdoor or external winds even

when the product is not operated. It is recommended to install an Electrically operated damper to  block the outdoor air.

3.In a cold weather area, an area with strong external winds or where fog occurs frequently, cold outdoor air, external winds

or fog may be introduced into the product when its operation is stopped.

It is recommended to install an Electrically operated damper.

4.In a cold weather area, or others, dewing or freezing could occur on the main unit, where the duct is connected, or other

sections, depending on the conditions of outdoor air and indoor temperature and moisture, even if they are within the
range of operating conditions.  Make sure to confirm the operating conditions and  other precautions, and do not use the
product if dewing or freezing is anticipated.

5.The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor louvres from LOSSNAY, and prop-

erly insulated. (The entry of rain water may cause power leakage, fire, or damege to household property)

6.The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming.

If it is expected that the ambient temperature around the place where the LOSSNAY unit is installed will be high during the

summer air conditioning season, it is recommended that the indoor ductwork be covered with insulation material. 

7.Inspection opening (450 

× 

450 or 600 

× 

600mm)must be installed on the filter and LOSSNAY core removing side.

LOSSNAY model selection advices

1.Operating environment  

Install this product in an environment where the temperature ranges from -10

°

C to +40

°

C and the relative humidity is

less than 80%RH. If condensation is expected to form,heat up the fresh outside air should be treated.  

2.Do not use under high temperature and humidity condition  

Condensation will occur and water will gather inside the LOSSNAY cores under high temperature and humidity condition,

such as warm swimming pool, bathroom, greenhouse or foggy place. 

3.Condition of outdoor, indoor and return air  

Avoid using LOSSNAY under air condition with acid, alkalis, organic solvent , oil mist, paint, or harmful gas as  presticide,

corrosive gas, etc.

4.Insulation failure caused by salt or sulphur air and hot spring steam, Rust, fire or malfunction may occur.   

Installing high quality filters inside outdoor air duct if the LOSSNAY operates in salt or sulphur air conditions.

5.Intake of mist or outdoor air during off-mode operation  

Outdoor air or mist may flow through the duct into your room when LOSSNAY is in off-mode at windy and foggy area.
To prevent intake of outdoor air or fog, a damper is advised to be installed.

6.Entry of insects  

When using the product in an environment where there is a window,or opening near the outdoor hood,so that insects are

likely to gather around the interior or exterior light,take note that small insects may intrude into the LOSSNAY filters.

7.By-pass ventilation

In the case of "By-pass" ventilation, the supply air temperature slightly rises more than the outside air temperature.

because of the effect around the ducts or the unit motors.

8.Usage of M-NET.

When solely using LOSSNAY units, power supply unit is required to connect to centralized control. Number of power sup-

ply units or the transmission boosters should correspond with the connected LOSSNAY units.

Caution for installation

1.Do not modify the unit as it may cause malfunction.
2.Leaving sufficient space for maintenance purpose.
3.The location of the air inlet 

Take care in locating air inlet to prevent intake of dirty air or disgusting smell from exhaust gas of factory, air from rubbish

disposal, etc.

4.Take precautions when using the product in quiet location.
5.Heat insulation foam for duct 

Take care as below to prevent the contaminate ceiling by duct condensation.
1)The two outdoor ducts(OA and EA) must be covered with heat-insulating material in order to prevent condensation.
2)If it is expected that the ambient temperature around the place where the LOSSNAY unit is installed will be high during

the summer air conditioning season, it is recommended that the indoor ductwork be covered with insulation material.

3)Outdoor air may come into unit during not operating unit by the pressure difference between indoor and outdoor or the

outdoor wind. In this case you should install a damper.

4)It is possible for condensation and freezing to occur in the cold regions inside the unit because of the outdoor air

condition or humidity condition above ceiling. Make sure to install supplemental insulation foam.

5)In the case that air condition around LOSSNAY unit is high temperature in summer, it is recommended that there are

heat insulation foam on indoor side duct to prevent heat recovery decreased by warming indoor duct.
In winter, it is possible to cool indoor side duct without heat insulation foam on indoor side duct.

6.Prevent entry of rainwater into LOSSNAY unit

Install weather louvre or "Weather cover" for OA inlet & EA outlet. This is to prevent rainwater entering the LOSSNAY unit.
Ducts to outdoor (OA and EA) should decline by 1/30 or more.
1)Install the anchor bolts to ensure the product's weight or earthquake load. (Correctly rated wire/chain may also be used)
2)Do not install this product in a place where it is exposed to ultraviolet light. (UV may be damage covering insulation.)

7.Electrical Work

A single pole isolator must be installed at the origins of mains power supply. 
Use single flush box, to support remote controller.  
Must connect ground wiring.
When connecting external devices (electrically operated damper, lamp, monitoring unit, etc.) using output signals of the

LOSSNAY unit, make sure to install safety equipment for the external devices.

(It could cause fire, damage, etc. without safety equipment)

LGH-15RX

5

LGH-25RX

5

LGH-35RX

5

LGH-50RX

5

LGH-65RX

5

LGH-80RX

5

LGH-100RX

5

A

768

768

875

875

895

1010

1010

Model

B

782

782

921

1063

1001

1036

1263

Unit: mm

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...U TOKYO 100 8310 JAPAN http Global MitsubishiElectric com Y08 003 Nov 2008 MEE Specifications subject to change without notice C o n c e n t r a t i n g w h a t w e c a n d o m o r e e v e r a n d d e f i n i t e l y ENERGY RECOVERY VENTILATORS RX5 SERIES MODEL ...

Page 2: ...50 38 5kJ kg DA 33ºC 20 1g kg DA 63 84 6kJ kg DA 26ºC 10 5g kg DA 50 52 9kJ kg DA Energy recovery calculating equation Indoor supply air temperature ºC Indoor temperature ºC Outdoor temperature ºC _ Temp recovery efficiency Outdoor temperature ºC Calculation example 16ºC 20ºC _ 0ºC 80 0ºC Energy recovery calculating equation Indoor supply air temperature ºC Outdoor temperature ºC Indoor temperatur...

Page 3: ...uilding during the cooling season such as early morning or at night By pass ventilation will draw in the cooler outside air and reduce the cooling load on the system 2 Night purge By pass ventilation can be used to release hot air from inside the building that has accumulated in buildings a business district during the hot summer season 3 Office equipment room cooling During cold season fresh air ...

Page 4: ...er than the room temperature ventilation starts automatically The air conditioning load required to reach the set temperature the next morning is reduced At night the outside temperature drops When the room becomes sufficiently cool ventilation is stopped Hot air is discharged Example B Weekly Example A Hourly 8 00 9 00 12 00 13 00 17 00 19 00 22 00 low high low high low extra low new RX5 series w...

Page 5: ... units and general equipment To operate general equipment PAC YG66DCA is required Switches between Cool Dry Auto Fan Heat Group of LOSSNAY unit automatic ventilation vent heat interchange normal ventilation depending on the air conditioner unit Auto mode is for City Multi R2 and WR2 series only Cool Dry 19 67 30 87 14 57 30 87 Heat 17 63 28 83 17 63 28 83 Auto 19 67 28 83 17 63 28 83 in case of us...

Page 6: ...olyolefin EU F7 Standard filter High efficiency filter EA OA Lighting etc Replacement components for the standard air filter supplied with the LOSSNAY LGH main unit Model Applicable model PZ 25RF8 E PZ 35RF8 E PZ 50RF8 E PZ 65RF8 E PZ 80RF8 E PZ 100RF8 E LGH 15RX5 E LGH 25RX5 E LGH 35RX5 E LGH 50RX5 E LGH 65RX5 E LGH 80RX5 E LGH 150RX5 E 2sets LGH 100RX5 E LGH 200RX5 E 2sets Filter material Dimens...

Page 7: ... back for more Cleanliness is the key to an attractive atmos phere and restaurants devote significant effort to ensuring the premises are sanitary Sanitation and cleanliness how ever are not enough No matter how clean a restaurant may look if there are bothersome odors lingering in the air all those efforts go to waste and the restaurant s clean image is tarnished For these reasons we invite resta...

Page 8: ...a high Air volume L s O mmH 2 0 30 25 20 15 10 5 Pa m2 h 300 250 50 100 150 200 250 200 150 100 50 0 20m 10m 5m 15m 50Hz Single phase 240V Exchange efficiency External static pressure 50 60 70 80 90 100mm length dia pipe 10 20 30 40 50 60 70 0 High Unit mm LGH 15 to 100RX5 LGH 150 and 200RX5 LGH 15RX5 E Frequency Power source Ventilation mode Fan speed Current A Power consumption W Air volume Mode...

Page 9: ...where duct direction 63 63 65 65 Inspection opening Extra low Extra high Low Temperature exchange efficiency efficiency Cooling Enthalpy exchange efficiency Heating Enthalpy exchange 25 20 0 150 90 80 70 60 50 Exchange efficiency 50Hz Single phase 240V 30m 20m 10m External static pressure 5 10 15 Pa O 2 H m m 100 90 80 70 60 40 50 Air volume L s m2 h length pipe 40m dia 400 50 100 30 150 200 250 3...

Page 10: ...ore air filter High Position where duct direction Inspection opening 208 192 Extra low Temperature exchange efficiency Enthalpyexchange efficiency Heating Enthalpy exchange efficiency Cooling Extra high Low High Unit mm LGH 50RX5 E LGH 65RX5 E Ventilation mode Fan speed Current A Power consumption W Air volume Model External static pressure Temperature exchange efficiency Enthalpy exchange efficie...

Page 11: ...pection opening 258 242 Low efficiency Heating Enthalpy Temperature exchange efficiency Enthalpy exchange efficiency Cooling exchange Extra high Extra low High 50Hz Single phase 240V External static pressure m 2 H m O 10 20 Exchange efficiency 0 m2 h 350 50 100 150 200 250 300 250mm length pipe dia 50 60 70 80 90 Pa 40 30 50 0 500 100 200 300 400 1200 1000 800 600 400 200 0 100m 60m 20m 40m 80m Ai...

Page 12: ...se 240V Pa Enthalpy exchange efficiency Cooling efficiency Heating Enthalpy exchange Temperature exchange efficiency Low High Extra high 90 80 70 60 50 External static pressure Exchange efficiency 0 500 1000 1500 2000 2500 300 200 100 400 500 m2 h 0 700 600 500 400 300 200 100 Air volume L s 10 20 30 40 50 0 2 H m m O Unit mm LGH 150RX5 E LGH 200RX5 E Ventilation mode Fan speed Current A Power con...

Page 13: ... controller Max 2remote controllers installable cable 2nd LOSSNAY unit Up to max 15 units 1 LGH 150RX5 and 200RX5 Definition of Symbols M1 Motor for exhaust fan X10 X11 X12 Relay contact M2 Motor for supply fan X101 X102 X103 Relay Supply fan speed control C Capacitor X201 X202 X203 Relay Exhaust fan speed control GM Motor for By pass operation CN1 Connector Transformer primary LS Microswitch CN2 ...

Page 14: ...nt condensation from forming If it is expected that the ambient temperature around the place where the LOSSNAY unit is installed will be high during the summer air conditioning season it is recommended that the indoor ductwork be covered with insulation material 7 Inspection opening 450 450 or 600 600mm must be installed on the filter and LOSSNAY core removing side LOSSNAY model selection advices ...

Reviews: