6 N:N NETWORK
6.1 System Configuration
87
6
6
N:N NETWORK
LE7-40GU can be operated as a local station for FX PLC N:N network communication.
Data monitoring and parameter writing from a master station FX PLC for up to seven local stations (LE7-40GU units) can be
carried out.
Precautions
• For 5 seconds after turning on the power of LE7-40GU, data from master station will not be accepted.
• Initial setting of LE7-40GU can not be done only with N:N Network.
• Simultaneous use of N:N Network and CC-Link communication is not possible.
6.1
System Configuration
6.2
Wiring
This section describes wiring.
Selection of cable
Use the following procedure to select cables.
Twisted pair cable
Use a shield twisted pair wire for connection with RS-485 communication equipment.
■
RS-485 cable specification
Connection equipment
Communication
form
Connection cable
Tension controller
(Local station)
Connectable
No. of units
Cable type name
Optional equipment
Main unit
FX5 PLC (master station)
RS-485
User created
(Built-in to main unit)
LE7-40GU
Up to seven local stations (LE7-
40GU) from the master station
Item
Specifications
Cable type
Shielded cable
Pairs
2 p, 3 p
Conductor resistance (20
)
88.0
/km or less
Insulation resistance
10000 M
-km or more
Withstand voltage
500 V DC1 minute
Capacitance (1 kHz)
An average of 60 nF/km or less
Characteristic impedance (100 kHz)
110
10
LE7-40GU
N:N Network master station
(FX series PLC)
Connection Cable
Summary of Contents for LE7-40GU
Page 1: ...LE7 40GU INSTRUCTION MANUAL Communication ...
Page 2: ......
Page 10: ...8 TRADEMARKS 150 ...
Page 11: ...9 CONTENTS ...
Page 37: ...3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program 35 3 ...
Page 38: ...36 3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program ...
Page 39: ...3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program 37 3 ...
Page 40: ...38 3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program ...
Page 57: ...4 SLMP COMMUNICATION 4 3 Reference Program 55 4 Program example ...
Page 58: ...56 4 SLMP COMMUNICATION 4 3 Reference Program ...
Page 59: ...4 SLMP COMMUNICATION 4 3 Reference Program 57 4 ...
Page 60: ...58 4 SLMP COMMUNICATION 4 3 Reference Program ...
Page 61: ...4 SLMP COMMUNICATION 4 3 Reference Program 59 4 ...
Page 82: ...80 5 MODBUS TCP SLAVE 5 3 Reference Program Program example ...
Page 83: ...5 MODBUS TCP SLAVE 5 3 Reference Program 81 5 ...
Page 84: ...82 5 MODBUS TCP SLAVE 5 3 Reference Program ...
Page 85: ...5 MODBUS TCP SLAVE 5 3 Reference Program 83 5 ...
Page 86: ...84 5 MODBUS TCP SLAVE 5 3 Reference Program ...
Page 110: ...108 6 N N NETWORK 6 4 Reference Program Program example ...
Page 111: ...6 N N NETWORK 6 4 Reference Program 109 6 ...
Page 112: ...110 6 N N NETWORK 6 4 Reference Program ...
Page 147: ...7 MODBUS RTU ASCII SLAVE 7 4 Reference Program 145 7 Function code H03 Read holding register ...
Page 149: ...7 MODBUS RTU ASCII SLAVE 7 4 Reference Program 147 7 ...
Page 153: ......