Installation and operation manual
KSGD02 Revision: 1.4
Page 9 of 16
R
KSGD-01WS-B
2.2 Electrical connections
The KSGD connections are located on the rear of the detector PCB.
The KSGD will operate from a 12/24 volt AC or DC supply. Start-up current from a 24 volt AC supply
is 260mA with steady state of 100mA. A single plug on the PCB accepts all the electrical connections.
A small flat bladed screwdriver can be used to prise the plug away from the socket.
Dual relay version;
Pin Usage
1
Power (V1) 12 to 24V
AC or DC
2
Power (V2)
3
Relay 1 (NO1) Normally
Open
4
Relay 1 (C1) Common
5
Relay 2 - (NC2) Normally
Closed
6
Relay 2 (C2) Common
Single relay version;
See section 3 for details on the relay operation and functions.
Relay(s) are energized in normal operation, the relay will de-energize if an alarm or fault
occurs or if power is not present. The tables above show the relay(s) in the de-energized
power removed state.
Pin Usage
1
Power (V1) 12 to 24V
AC or DC
2
Power (V2)
3
Relay (NO) Normally
Open
4
Relay (C) Common
5
Relay (NC) Normally
Closed
Fig 2.2 KSGD dual relay version
Fig 2.3 KSGD single relay version
i
6
5 4 3 2 1
Connection Terminals
Test / Calibration
connector
5
4 3 2 1
Connection Terminals
Test / Calibration
connector