100
2.6.2
Setting dial function selection (Pr. 53
)
Using the setting dial like a potentiometer to perform operation
Refer to
(page 99).
You can use the dial like a potentiometer to perform operation.
Parameter
Name
Factory
Setting
Setting
Range
Remarks
53
Frequency setting
operation selection
0
0, 1
0: Setting dial
frequency setting
mode
1: Setting dial
potentiometer mode
Setting is
enabled when
Pr. 30 = "1"
POINT
•
Set "1" (extended function parameter valid) in Pr. 30 "extended function display
selection".
•
Set "1" (setting dial potentiometer mode) in Pr. 53 "frequency setting operation
selection".
Operation example Changing the frequency from 0Hz to 60Hz during operation
REMARKS
•
If flickering "60.0" turns to "0.0", the Pr. 53 "frequency setting operation selection" setting
may not be "1".
•
Independently of whether the inverter is running or at a stop, the frequency can be set by
merely turning the dial.
•
When the frequency is changed, it will be stored as the set frequency after 10s.
Choose monitor/frequency monitor. ( )
The inverter must be in the PU operation mode.
(Press the .)
Pr. 30 must be set to "1".
Pr. 53 must be set to "1".
1.
PU
EXT
Mode/monitor check
RUN
PU
EXT
MODE
RUN
PU
EXT
RUN
3.
Turn the clockwise until appears.
the set frequency.
You need not press the .
2.
Press the to start the inverter.
RUN
SET
Flickers for 3s.
Display
Operation
The flickering frequency is
"60.0"