17
PARAMETER LIST
332
RS-485
communication speed
3, 6, 12, 24,
48, 96, 192, 384
96
333
RS-485
communication stop
bit length
0, 1, 10, 11
1
334
RS-485
communication parity
check selection
0, 1, 2
2
335
RS-485
communication
number of retries
0 to 10, 9999
1
336
RS-485
communication
check time interval
0 to 999.8s,
9999
0s
337
RS-485
communication
waiting time setting
0 to 150ms,
9999
9999
338
Communication
operation command
source
0, 1
0
339
Communication
speed command
source
0, 1, 2
0
340
Communication
startup mode
selection
0, 1, 2, 10, 12
0
341
RS-485
communication
CR/LF selection
0, 1, 2
1
342
Communication
EEPROM write
selection
0, 1
0
343
Communication
error count
⎯
0
495
Remote output
selection
0, 1, 10, 11
0
496
Remote output data 1
0 to 4095
0
497
Remote output data 2
0 to 4095
0
503
Maintenance timer
0 (1 to 9998)
0
504
Maintenance timer
alarm output set time
0 to 9998,
9999
9999
522
Output stop
frequency
0 to 400Hz,
9999
9999
539
Modbus-RTU
communication
check time interval
0 to 999.8s,
9999
9999
549
Protocol selection
0, 1
1
550
NET mode operation
command source
selection
0, 1, 9999
9999
551
PU mode operation
command source
selection
1, 2
2
553
PID deviation limit
0 to 100.0%,
9999
9999
554
PID signal operation
selection
0 to 3, 10 to 13
0
555
Current average
time
0.1 to 1.0s
1s
556
Data output mask
time
0.0 to 20.0s
0s
557
Current average
value monitor signal
output reference
current
Rated
inverter
current
Parameters
Name
Setting
Range
Initial
Value
563
Energization time
carrying-over times
(0 to 65535)
0
564
Operating time
carrying-over times
(0 to 65535)
0
570
Multiple rating
setting
0, 1
0
571
Holding time at a
start
0.0 to 10.0s,
9999
9999
573
4mA input check
selection
1,9999
9999
575
Output interruption
detection time
0 to 3600s,
9999
1s
576
Output interruption
detection level
0 to 400Hz
0Hz
577
Output interruption
cancel level
900 to 1100%
1000%
578
Auxiliary motor
operation selection
0 to 3
0
579
Motor switchover
selection
0 to 3
0
580
MC switching
interlock time
0 to 100s
1s
581
Start waiting time
0 to 100s
1s
582
Auxiliary motor
connection-time
deceleration time
0 to 3600/360s,
9999
1s
583
Auxiliary motor
disconnection-time
acceleration time
0 to 3600/360s,
9999
1s
584
Auxiliary motor 1
starting frequency
0 to 400Hz
60Hz
585
Auxiliary motor 2
starting frequency
0 to 400Hz
60Hz
586
Auxiliary motor 3
starting frequency
0 to 400Hz
60Hz
587
Auxiliary motor 1
stopping frequency
0 to 400Hz
0Hz
588
Auxiliary motor 2
stopping frequency
0 to 400Hz
0Hz
589
Auxiliary motor 3
stopping frequency
0 to 400Hz
0Hz
590
Auxiliary motor start
detection time
0 to 3600s
5s
591
Auxiliary motor stop
detection time
0 to 3600s
5s
611
Acceleration time at
a restart
0 to 3600s,
9999
5/15s
653
Speed smoothing
control
0 to 200%
0
654
Speed smoothing
cutoff frequency
0 to 120Hz
20Hz
799
Pulse increment
setting for output
power
0.1kWh,
1kWh, 10kWh,
100kWh,
1000kWh
1kWh
867
AM output filter
0 to 5s
0.01s
869
Current output filter
0 to 5s
0.02s
872
Input phase loss
protection selection
0, 1
0
882
Regeneration
avoidance operation
selection
0, 1, 2
0
Parameters
Name
Setting
Range
Initial
Value
*1
The setting depends on capacities. (FR-F720-02330 (FR-F740-01160) or less/FR-F720-03160 (FR-F740-01800) or more)