15
PARAMETER LIST
122
PU communication
check time interval
0, 0.1 to 999.8s,
9999
9999
123
PU communication
waiting time setting
0 to 150ms,
9999
9999
124
PU communication
CR/LF selection
0, 1, 2
1
125
Terminal 2
frequency setting
gain frequency
0 to 400Hz
60Hz
126
Terminal 4
frequency setting
gain frequency
0 to 400Hz
60Hz
127
PID control automatic
switchover frequency
0 to 400Hz,
9999
9999
128
PID action selection
10, 11, 20, 21,
50, 51, 60, 61,
110, 111, 120,
121
10
129
PID proportional
band
0.1 to 1000%,
9999
100%
130
PID integral time
0.1 to 3600s,
9999
1s
131
PID upper limit
0 to 100%,
9999
9999
132
PID lower limit
0 to 100%,
9999
9999
133
PID action set point
0 to 100%,
9999
9999
134
PID differential time
0.01 to 10.00s,
9999
9999
135
Electronic bypass
sequence selection
0, 1
0
136
MC switchover
interlock time
0 to 100s
1s
137
Waiting time at a
start
0 to 100s
0.5s
138
Bypass selection at
a fault
0, 1
0
139
Automatic
switchover
frequency from
inverter to bypass
operation
0 to 60Hz,
9999
9999
140
Backlash
acceleration
stopping frequency
0 to 400Hz
1Hz
141
Backlash
acceleration
stopping time
0 to 360s
0.5s
142
Backlash
deceleration
stopping frequency
0 to 400Hz
1Hz
143
Backlash
deceleration
stopping time
0 to 360s
0.5s
144
Speed setting
switchover
0, 2, 4, 6, 8,
10, 102, 104,
106, 108, 110
4
145
PU display language
selection
0 to 7
1
148
Stall prevention
level at 0V input.
0 to 120%
110%
149
Stall prevention
level at 10V input.
0 to 120%
120%
Parameters
Name
Setting
Range
Initial
Value
150
Output current
detection level
0 to 120%
110%
151
Output current
detection signal
delay time
0 to 10s
0s
152
Zero current
detection level
0 to 150%
5%
153
Zero current
detection time
0 to 10s
0.5s
154
Voltage reduction
selection during
stall prevention
operation
0, 1
1
155
RT signal reflection
time selection
0, 10
0
156
Stall prevention
operation selection
0 to 31, 100,
101
0
157
OL signal output
timer
0 to 25s, 9999
0s
158
AM terminal
function selection
1 to 3, 5, 6,
8 to 14, 17, 21,
24, 50, 52, 53
1
159
Automatic
switchover
frequency range
from bypass to
inverter operation
0 to 10Hz,
9999
9999
160
User group read
selection
0, 1, 9999
0
161
Frequency setting/
key lock operation
selection
0, 1, 10, 11
0
162
Automatic restart after
instantaneous power
failure selection
0, 1, 10, 11
0
163
First cushion time
for restart
0 to 20s
0s
164
First cushion
voltage for restart
0 to 100%
0%
165
Stall prevention
operation level for
restart
0 to 120%
110%
166
Output current
detection signal
retention time
0 to 10s, 9999
0.1s
167
Output current
detection operation
selection
0, 1, 10, 11
0
168
Parameter for manufacturer setting.
Do not set.
169
170
Cumulative power
meter clear
0, 10, 9999
9999
171
Operation hour
meter clear
0, 9999
9999
172
User group
registered display/
batch clear
9999, (0 to 16)
0
173
User group
registration
0 to 999, 9999
9999
174
User group clear
0 to 999, 9999
9999
178
STF terminal
function selection
0 to 8, 10 to 12,
14, 16, 24, 25,
60, 62, 64 to 67,
70 to 72, 9999
60
Parameters
Name
Setting
Range
Initial
Value
*1
Setting of "9" can be made for the FR-F720-03160 (FR-F740-01800) or more.