116
Function assignment of external
terminal and control
*1
When
Pr. 59 Remote function selection
≠
"0", the functions of the RL, RM and RH signals change as listed above.
*2
The OH signal turns on when the relay contact "opens".
2
RH
Pr. 59
= 0 (initial value)
High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr.
232 to Pr. 239
Pr. 59
≠
0
*1
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44 to Pr. 51
4
AU
Terminal 4 input selection
Pr. 267
5
JOG
Jog operation selection
Pr. 15, Pr. 16
6
CS
Selection of automatic restart after instantaneous power failure,
flying start
Pr. 57, Pr. 58, Pr.162 to Pr.165,
Pr. 299, Pr. 611
Electronic bypass function
Pr. 57, Pr. 58 Pr. 135 to Pr. 139,
Pr. 159
7
OH
External thermal relay input
*2
Pr. 9
8
REX
15 speed selection (combination with three speeds RL, RM, RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr.232 to Pr.239
10
X10
Inverter operation enable signal (FR-HC, MT-HC/FR-CV connection)
Pr. 30
11
X11
FR-HC or MT-HC connection, instantaneous power failure detection
Pr. 30
12
X12
PU operation external interlock
Pr. 79
14
X14
PID control valid terminal
Pr. 127 to Pr. 134, Pr. 575 to Pr.
577
16
X16
PU-external operation switchover
(external operation when X16 turns on)
Pr. 79, Pr. 340
24
MRS
Output stop
Pr. 17
Electronic bypass function
Pr. 57, Pr. 58, Pr. 135 to Pr. 139,
Pr. 159
25
STOP
Start self-holding selection
⎯
60
STF
Forward rotation command
(assigned to STF terminal
(Pr. 178)
only)
⎯
61
STR
Reverse rotation command
(assigned to STR terminal
(Pr. 179)
only)
⎯
62
RES
Inverter reset
⎯
⎯
63
PTC
PTC thermistor input (assigned to AU terminal
(Pr. 184)
only)
Pr. 9
64
X64
PID forward/reverse action switchover
Pr. 127 to Pr. 134
65
X65
PU-NET operation switchover
(PU operation when X65 turns on)
Pr. 79, Pr. 340
66
X66
External-NET operation switchover
(NET operation when X66 turns on)
Pr. 79, Pr. 340
67
X67
Command source switchover
(
Pr.338
and
Pr.339
commands are valid when X67 turns on)
Pr. 338, Pr. 339
70
X70
DC feeding operation permission
Pr. 30, Pr. 70
71
X71
DC feeding cancel
Pr. 30, Pr. 70
72
X72
PID integral value reset
Pr. 127 to Pr. 134, Pr. 241, Pr.
553, Pr. 554, Pr. 575 to Pr. 577,
C42 to C45
9999
⎯
No function
⎯
⎯
REMARKS
⋅
Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
⋅
The priorities of the speed commands are in order of jog > multi-speed setting (RH, RM, RL, REX) > PID (X14).
⋅
When the X10 signal (FR-HC, MT-HC, FR-CV connection - inverter operation enable signal) is not set or when the PU
operation external interlock (X12) signal is not assigned at the
Pr. 79 Operation mode selection
setting of "7", the MRS signal
shares this function.
⋅
Same signal is used to assign multi-speeds (7 speeds) and remote setting. They cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same time .)
CAUTION
⋅
Changing the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Also
check that wiring is correct, since the terminal name and the signal function became different. Please make setting after
confirming the function of each terminal.
Setting
Signal
Name
Function
Related Parameters
Refer to
Page