96
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
4.7 Setting of acceleration/deceleration time and
acceleration/deceleration pattern
4.7.1
Setting of the acceleration and deceleration time (Pr.7, Pr.8, Pr.20, Pr.21, Pr.44, Pr.45)
Purpose
Parameter that must be set
Refer to page
Motor acceleration/deceleration time
setting
Acceleration/deceleration times
Pr.7, Pr.8, Pr.20, Pr.21,
Pr.44, Pr.45
Starting frequency
Starting frequency and start-
time hold
Pr.13, Pr.571
Set acceleration/deceleration pattern
suitable for application
Acceleration/deceleration
pattern and backlash measures
Pr.29, Pr.140 to Pr.143
Used to set motor acceleration/deceleration time.
Set a larger value for a slower speed increase/decrease or a smaller value for a faster speed increase/
decrease.
For the acceleration time at automatic restart after instantaneous power failure, refer to
Pr. 611 Acceleration
time at a restart
(page 141)
.
Parameter
Number
Name
Initial Value
Setting Range
Description
7
Acceleration time
7.5K or less
5s
0 to 3600/ 360s
*2
Set the motor acceleration time.
11K or more
15s
8
Deceleration time
7.5K or less
10s
0 to 3600/ 360s
*2
Set the motor deceleration time.
11K or more
30s
20
*1
Acceleration/
deceleration
reference frequency
60Hz
1 to 400Hz
Set the frequency that will be the basis of
acceleration/deceleration time.
As acceleration/deceleration time, set the
frequency change time from stop to
Pr. 20
.
21
*1
Acceleration/
deceleration time
increments
0
0
Increments: 0.1s
Range: 0 to 3600s
Increments and
setting range of
acceleration/
deceleration time
setting can be
changed.
1
Increments: 0.01s
Range: 0 to 360s
44
*1
Second
acceleration/
deceleration time
5s
0 to 3600/360s
*2
Set the acceleration/deceleration time
when the RT signal is on.
45
*1
Second
deceleration time
9999
0 to 3600/360s
*2
Set the deceleration time when the RT
signal is on.
9999
Acceleration time = deceleration time
*1
The parameters can be set when
Pr. 160 User group read selection
= "0"
(Refer to page 175)
*2
Depends on the
Pr. 21 Acceleration/deceleration time increments
setting. The initial value for the setting range is "0 to 3600s" and the setting
increments is "0.1s".
(1) Acceleration time setting
(Pr.7, Pr.20)
⋅
Use
Pr. 7 Acceleration time
to set the acceleration time required to reach
Pr.
20 Acceleration/deceleration reference frequency
from 0Hz.
⋅
Set the acceleration time according to the following formula.
Example) How to find the setting value for
Pr.7
when increasing the output
frequency to the maximum frequency of 50Hz in 10s with
Pr.20
=
60Hz (initial setting) and
Pr.13
= 0.5Hz.
Acceleration
time setting
=
Pr.20
×
Acceleration time from stop to
maximum operating frequency
Maximum operating
frequency -
Pr. 13
Running
frequency
Acceleration
time
Deceleration
time
Time
Pr.20
Pr.7
Pr.8
Output
frequency
(Hz)
(60Hz)
Pr.7
=
60Hz
×
10s
12.1s
50Hz - 0.5Hz