Selection and protection of a motor
4
4.8.2
Applied motor (Pr. 71)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 175)
Refer to the following list and set this parameter according to the motor used.
Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is necessary when using a constant-torque motor. Thermal characteristic of the electronic thermal relay
function suitable for the motor is set.
Parameter
Number
Name
Initial Value
Setting Range
Description
71
Applied motor
0
0, 1, 2, 20
Selecting the standard motor or constant-
torque motor sets the corresponding motor
thermal characteristic.
Pr. 71
Setting
Thermal Characteristic of the Electronic Thermal Relay Function
Motor (
{
: used motor)
Standard
(SF-JR, etc.)
Constant-torque
(SF-HRCA, etc.)
0
(initial value)
Thermal characteristics of a standard motor
{
1
Thermal characteristics of the Mitsubishi constant-torque motor
{
2
Thermal characteristics of a standard motor
Adjustable 5 points V/F
(Refer to page 87)
{
20
Mitsubishi standard motor SF-JR 4P(1.5kW or less)
{
REMARKS
⋅
For the 5.5K and 7.5K, the
Pr. 0 Torque boost
and
Pr. 12 DC injection brake operation voltage
settings are automatically changed
according to the
Pr. 71
setting as follows.
CAUTION
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
♦
Parameters referred to
♦
Pr. 0 Torque boost
Refer to page 74
Pr. 12 DC injection brake operation voltage
Refer to page 106
Pr. 100 to Pr. 109 (Adjustable 5 points V/F)
Refer to page 87
Pr. 71
Standard Motor Setting
0, 2, 20
Constant-torque Motor Setting
1
Pr. 0
3%
2%
Pr. 12
4%
2%