2. Basic Operation
2.7 Basic operation procedure (JOG operation)
2.7
Basic operation procedure (JOG operation)
2.7.1
Giving a start command by using external signals
for JOG operation
• The JOG signal can be input only via a control terminal.
• JOG operation is performed while the JOG signal is ON.
• Use
Pr.15 Jog frequency
to set a frequency, and set
Pr.16 Jog acceleration/deceleration time
to set the acceleration/
deceleration time for JOG operation.
• Set
Pr.79 Operation mode selection
= "2" (External operation mode).
[Connection diagram]
The following shows the procedure to operate at 5 Hz.
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Assignment of JOG signal
Set
Pr.180 RL terminal function selection
= "5" to assign the JOG signal to terminal RL.
3.
Turning ON the JOG signal
Turn ON the JOG switch (JOG signal). The inverter is set ready for the JOG operation.
4.
Start
→
acceleration
→
constant speed
Turn ON the start switch (STF/STR signal). The frequency value on the monitor increases according to the setting
of
Pr.16 Jog acceleration/deceleration time
, and "5.00" (5.00 Hz) appears on the monitor. The RUN LED is ON
during forward rotation and blinks slowly during reverse rotation.
5.
Deceleration
→
stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of
Pr.16 Jog acceleration/deceleration time
, "0.00" (0.00 Hz) appears on the monitor, and the motor stops
rotating. The RUN LED turns OFF. Turn OFF the JOG switch (JOG signal).
NOTE
• To change the frequency, change the setting of
Pr.15 Jog frequency
(initial value: 5 Hz).
• To change the acceleration/deceleration time, change the setting of
Pr.16 Jog acceleration/deceleration time
(initial value:
0.5 seconds).
• The JOG signal can be assigned to another terminal. Set "5" in any parameter from
Pr.178 to Pr.184 (Input terminal function
selection)
to assign the function to an input terminal. (For the Ethernet model, assign the signal to terminal DI0 or DI1 using
Pr.178 or Pr.179
.)
• The JOG2 signal enables the JOG operation via communication. (Refer to
Parameters referred to
Pr.15 Jog frequency, Pr.16 Jog acceleration/deceleration time
Pr.79 Operation mode selection
STF
Forward rotation start
SD
RL(JOG)
Inverter
JOG signal
Reverse rotation start
STR
Switch
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...