Function assignment of external terminals
Parameter
6 - 104
Output frequency detection (FU, Pr. 42, Pr. 43)
The output frequency detection signal (FU) is output when the output frequency reaches or ex-
ceeds the Pr. 42 setting. This function can be used for electromagnetic brake operation, open
signal, etc.
When the detection frequency is set to Pr. 43, frequency detection for reverse operation use only
can also be set. This function is effective for switching the timing of electromagnetic brake op-
eration between forward rotation (rise) and reverse rotation (fall) during vertical lift operation,etc.
When Pr. 43
≠
9999, the Pr. 42 setting is used for forward rotation and the Pr. 43 setting is used
for reverse rotation.
The FU signal can also be assigned to the other terminal by setting "4" (positive logic) or "104"
(negative logic) in any of Pr. 190, Pr. 192 or Pr. 197.
I001798E
Fig. 6-54:
Frequency detection for forward and reverse rotation
NOTES
All signals are off during DC injection brake.
The output frequency to be compared with the set frequency is the output frequency before
slip compensation is performed.
Changing the terminal assignment using Pr. 190, Pr. 192 or Pr. 197 may affect the other
functions. Make setting after confirming the function of each terminal.
FU
Output
frequency
Time
Forward
rotation
Reverse
rotation
ON
ON
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......