116
Function assignment of external terminal and control
(2) Inverter operation ready signal (RY signal) and inverter running signal (RUN signal)
When the inverter is ready to operate, the output of the operation ready signal (RY) is on. (It is also on during inverter running.)
When the output frequency of the inverter rises to or above
Pr. 13 Starting frequency
, the output of the inverter running signal
(RUN) is turned on. During an inverter stop or DC injection brake operation, the output is off.
When using the RY and RUN signals, assign functions to
Pr.190 or Pr.192 (output terminal selection function)
referring to the
table below.
Output
Signal
Pr. 190 to Pr. 192
Setting
Positive logic
Negative logic
RY
11
111
RUN
0
100
Inverter
Status
Start
Signal
OFF
(during
stop)
Start
Signal ON
(during
stop)
Start
Signal ON
(during
operation)
Under DC
Injection Brake
At Alarm
Occurrence
or MRS Signal ON
(output shutoff)
Automatic Restart after
Instantaneous Power Failure
Coasting
Restarting
Output
signal
Start
signal
ON
Start
signal
OFF
RY
ON
ON
ON
ON
OFF
ON
∗1
ON
RUN
OFF
OFF
ON
OFF
OFF
OFF
ON
∗1
This signal turns OFF during power failure or undervoltage.
REMARKS
The RUN signal (positive logic) is assigned to the terminal RUN in the initial setting.
Time
Power supply
Output frequency
STF
RH
RY
Pr. 13 Starting frequency
ON
OFF
ON
OFF
ON
OFF
ON
DC injection brake operation point
DC injection brake operation
RUN
ON
OFF
Reset processing