Wiring protection
For installation Class T, Class J, Class CC, or Class L fuse, or UL 489 Molded Case Circuit Breaker (MCCB) according to the local direc
-
tives must be provided.
For the FR-A820 series, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
*1
Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
*2
Select an appropriate molded case circuit breaker with a rating that is suitable for the size of the cable.
For wiring protection of the converter unit (FR-CC2) refer to "FR-A802-R2R Instruction Manual (Hardware)".
A.1.3 Short circuit ratings
O
200 V class
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 240 V maximum.
O
400 V class
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 500 V maximum.
A.1.4 Machinery directive
The frequency inverter itself is not a machine in the spirit of the EU machinery directive. The start up of the frequency inverter in a
machine is prohibited so long until it has been confirmed that the entire machine complies with the provisions of Directive 98/37/
EC (from 29.12.2009 Machinery Directive 2006/42/EC).
FR-A820-
m
-R2R
00046
(0.4K)
00077
(0.75K)
00105
(1.5K)
00167
(2.2K)
00250
(3.7K)
00340
(5.5K)
00490
(7.5K)
00630
(11K)
00770
(15K)
00930
(18.5K)
01250
(22K)
01540
(30K)
Rated fuse voltage [V]
240 V or more
Fuse maximum
allowable rating
[A]
Without power factor
improving reactor
15
20
30
40
60
80
150
175
200
225
300
350
With power factor
improving reactor
15
20
20
30
50
70
125
150
200
200
250
300
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1 *2
15
15
25
40
60
80
110
150
190
225
300
350
FR-A820-
m
-R2R
01870
(37K)
02330
(45K)
03160
(55K)
03800
(75K)
04750
(90K)
Rated fuse voltage [V]
240 V or more
Fuse maximum
allowable rating
[A]
Without power factor
improving reactor
400
500
500
—
—
With power factor
improving reactor
350
400
500
600
700
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1 *2
450
500
700
900
1000
FR-A840-
m
-R2R
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
00620
(22K)
00770
(30K)
Rated fuse voltage [V]
500 V or more
Fuse maximum
allowable rating
[A]
Without power factor
improving reactor
6
10
15
20
30
40
70
80
90
110
150
175
With power factor
improving reactor
6
10
10
15
25
35
60
70
90
100
125
150
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1 *2
15
15
15
20
30
40
60
70
90
100
150
175
FR-A840-
m
-R2R
00930
(37K)
01160
(45K)
01800
(55K)
02160
(75K)
02600
(90K)
03250
(110K)
03610
(132K)
04320
(160K)
04810
(185K)
05470
(220K)
06100
(250K)
06830
(280K)
Rated fuse voltage [V]
500 V or more
Fuse maximum
allowable rating
[A]
Without power factor
improving reactor
200
250
300
—
—
—
—
—
—
—
—
—
With power factor
improving reactor
175
200
250
300
350
400
500
600
700
800
900
1000
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1 *2
225
250
450
450
500
—
—
—
—
—
—
—