32
BASIC OPERATION
155
RT signal function
validity condition
selection
0, 10
0
156
Stall prevention
operation selection
0 to 31, 100, 101
0
157
OL signal output timer 0 to 25 s, 9999
0 s
158
AM terminal function
selection
1 to 3, 5 to 14, 17,
18, 19, 21, 22, 24,
26 to 28, 30,
32 to 34, 36, 46,
50, 52 to 54, 61,
62, 67, 70,
81 to 84, 87 to 93,
97, 98
1
159
*16 DA1 output sign
selection
0 to 2
0
160
User group read
selection
0, 1, 9999
0
161
Frequency setting/key
lock operation
selection
0, 1, 10, 11
0
162
Automatic restart after
instantaneous power
failure selection
0 to 3, 10 to 13
0
163
First cushion time for
restart
0 to 20 s
0 s
164
First cushion voltage
for restart
0 to 100%
0%
165
Stall prevention
operation level for
restart
0 to 400%
150%
166
Output current
detection signal
retention time
0 to 10 s, 9999
0.1 s
167
Output current
detection operation
selection
0, 1, 10, 11
0
168
Parameter for manufacturer setting. Do not set.
169
170
Watt-hour meter clear 0, 10, 9999
9999
171
Operation hour meter
clear
0, 9999
9999
172
User group registered
display/batch clear
9999, (0 to 16)
0
173
User group
registration
0 to 1999, 9999
9999
174
User group clear
0 to 1999, 9999
9999
178
STF terminal function
selection
0 to 13, 16 to 18,
20, 23 to 28, 32,
42 to 44, 46 to 48,
50 to 53, 60, 62,
64 to 67, 70 to 72,
74, 81, 92, 93,
100 to 109,
111 to 117,
120 to 126, 9999
60
179
STR terminal function
selection
0 to 13, 16 to 18,
20, 23 to 28, 32,
42 to 44, 46 to 48,
50 to 53, 61, 62,
64 to 67, 70 to 72,
74, 81, 92, 93,
100 to 109,
111 to 117,
120 to 126, 9999
61
Parameter Name
Setting range
Initial value
Simple
Simple
Simple
180
RL terminal function
selection
0 to 13, 16 to 18,
20, 23 to 28, 32,
42 to 44, 46 to 48,
50 to 53,
62, 64 to 67,
70 to 72, 74, 81,
92, 93,
100 to 109,
111 to 117,
120 to 126, 9999
0
181
RM terminal function
selection
1
182
RH terminal function
selection
2
183
RT terminal function
selection
3
184
AU terminal function
selection
4
185
JOG terminal function
selection
5
186
CS terminal function
selection
6
187
MRS terminal function
selection
24
*14
10
*15
188
STOP terminal
function selection
25
189
RES terminal function
selection
62
190
RUN terminal function
selection
0 to 8, 10 to 16,
25, 26, 30 to 35,
39 to 48, 55, 64,
67, 68, 79, 80, 85,
90 to 99,
100 to 108,
110 to 116, 125,
126, 130 to 135,
139 to 148, 155,
164, 167, 168,
179, 180, 185,
190 to 199,
206 to 208,
211 to 213,
231 to 239, 242,
306 to 308,
311 to 313,
331 to 339, 342,
9999
*18
0
191
SU terminal function
selection
1
192
IPF terminal function
selection
2
*14
9999
*15
193
OL terminal function
selection
3
194
FU terminal function
selection
4
195
ABC1 terminal
function selection
0 to 8, 10 to 16,
25, 26, 30 to 35,
39 to 48, 55, 64,
67, 68, 79, 80, 85,
90, 91, 94 to 99,
100 to 108,
110 to 116, 125,
126, 130 to 135,
139 to 148, 155,
164, 167, 168,
179, 180, 185,
190, 191,
194 to 199,
206 to 208,
211 to 213,
231 to 239, 242,
306 to 308,
311 to 313,
331 to 339, 342,
9999
*18
99
196
ABC2 terminal
function selection
9999
232
to
239
Multi-speed setting
(speeds 8 to 15)
0 to 590 Hz, 9999
9999
240
Soft-PWM operation
selection
0, 1
1
241
Analog input display
unit switchover
0, 1
0
242
Terminal 1 added
compensation amount
(terminal 2)
0 to 100%
100%
Parameter Name
Setting range
Initial value
*14
The setting range or initial value is for standard models.
*15
The setting range or initial value is for separated converter types.
*16
The setting is available only when the FR-A8AZ is installed.
*18
The setting values "242" and "342" are available for the Ethernet models only.