INVERTER SETTING
4.6
Inverter Reset
(1) Operation conditions of inverter reset
Which resetting method is allowed or not allowed in each operation mode is described below.
*1
Inverter reset can be made any time.
*2
Reset can be made only when the protective function of the inverter is activated.
Resetting Method
Operation Mode
Network
Operation
External
Operation
PU
Operation
Reset from the
network
Inverter reset Index H2107
(Refer to page 94)
*1
Allowed
Disallowed
Disallowed
Reset node service
(Refer to page 62)
Allowed
Disallowed
Disallowed
Error reset at inverter fault
(Refer to
page 33)
*2
Pr.349
= 0
Allowed
Allowed
Allowed
Pr.349
= 1
Disallowed
Disallowed
Turn on the terminal RES-SD
Enabled
Enabled
Enabled
Switch off inverter power
Enabled
Enabled
Enabled
Reset from the
PU/DU
Inverter reset
Enabled
Enabled
Enabled
Reset at inverter fault
Enabled
Enabled
Enabled
CAUTION
1. When a communication line error has occurred, reset cannot be made from the network.
2. The inverter is set to the external operation mode if it has been reset in network operation mode in the
initial status.
To resume the network operation, the inverter must be switched to the network operation mode again.
Set a value other than "0" in
Pr. 340
to start in network operation mode.
(Refer to page 18.)
3. The inverter can not be controlled for about 1s after release of a reset command .