112
<Status transition>
Refer to the table below to send a command for status transition.
<Relationship between command and bit combination>
0 : OFF 1 : ON
: whichever is ok
Bit combination
Command
Bit7
Fault Reset
Bit3
Enable Operation
Bit2
Quick Stop
Bit1
Disable Voltage
Bit0
Switch On
Transition No
Shutdown
0
1
1
0
2, 6, 8
Switch On
0
1
1
1
3
Disable Voltage
0
0
7, 9, 10, 12
Quick Stop
0
0
1
7, 10, 11
Disable Operation
0
0
1
1
1
5
Enable Operation
0
1
1
1
1
4, 16
Fault Reset
0
⇒
1
15
Fault
Switched On
8
9
3
2
7
1
0
13
14
4
5
15
12
10
11
16
Power
Disabled
Fault
Power
Enabled
6
Start
Fault
Reaction Active
Not Ready to
Switch On *2
Switch On
Disabled *2
Ready to
Switch On
Operation
Enable *1
*1 The inverter outputs the speed of target_velocity at
transition to Operation Enable.
*2 During "Not Ready to Switch On" and "Switch On
Disabled" status, the inverter is in Output shutoff
status.
Main circuit capacitor life measuring does not
function.
Quick stop
Active
(number: Transition No)