INSTALLATION OF THE INVERTER AND INSTRUCTIONS
1 INSTALLATION OF THE INVERTER AND INSTRUCTIONS
•
Installation of the inverter
Note - Some inverter models may be installed outside an enclosure. See Appendix 1 for details.
•
General Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10
minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
•
Environment
Before installation, check that the environment meets following specifications.
Installation on the enclosure
REMARKS
To use an enclosed brake resistor for the FR-A760-00061 or less,
refer to page 4
.
Ambient temperature
-10°C to +40°C (14°F to 104°F) (non-freezing)
SLD of 00061 or less : -10°C to +30°C (14°F to 86°F)
(non-freezing)
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to + 65°C (-4°F to 149°F)
Ambience
Indoors (No corrosive and flammable gases, oil mist, dust and dirt.)
Altitude, vibration
Below 1000m, 5.9m/s
2
or less
CAUTION
• Install the inverter on a strong surface securely and vertically with bolts.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a non-combustible wall surface.
Capacity plate
Inverter type
Serial number
Capacity plate
Rating plate
110% 60s, 120% 3s
00061
NA
FR-A760-00061-NA
-
FR -
-
A760
Symbol
A760
Voltage Class
Three-phase
600V class
Symbol
600V class
00017 to 00840
Displays the
rated current
Type number
Rating plate
Inverter type
Input rating
Output rating
Serial number
FR-A760-00061-NA
LD (40 C) XXA
SLD (40 C) XXA
ND (40 C) XXA
HD (40 C) XXA
Overload current rating Ambient temperature
LD
120% 60s, 150% 3s
40 C (104 F)
ND
150% 60s, 200% 3s
40 C (104 F)
HD
200% 60s, 250% 3s
40 C (104 F)
•
Inverter Type
40 C (104 F)
30 C (86 F)(00061 or less)
SLD
FR-A760-00330 or less
FR-A760-00550 or more
CAUTION
• When encasing multiple inverters, install them in
parallel as a cooling measure.
• Install the inverter vertically.
5cm(1.97inches) or mor
e
*1
*1 1cm or more for FR-A760-00061 or less
Vertical
5cm
(1.97inches)
5cm
(1.97inches)
5cm
(1.97inches)
Measurement
position
Measurement
position
Inverter