DISPLAY UNIT for (Energy Measuring Unit)

Model

EMU4-D65

Instruction manual (Simplified edition)

 

Be sure to read this instruction manual and this equipment detail manual before use.

After reading on, you keep it in a safe place where you can be seen at any time, please read when needed

.

Please send this instruction manual to the end user.

You can download User’s manual of this Unit from the following site.

http://www.mitsubishielectric.com/fa/worldwide/index.html

1. Feature

The monitoring of measured data at Mitsubishi Energy Measuring Unit is possible.

Easily viewable by backlight and dot matrix LCD display.

Multiple circuit monitoring is possible using only one unit. 

It is possible to switch the display language (Japanese / English) in the setting.

2. Confirmation of contents of package

Each unit comes with the following accessories. Check for missing ones.

 

 

 

Main Body x 1

 

Connection cable x 1

 

Instruction manual

(Simplified edition) x 1

 

Switching board 

Installation screw x 2

3. Precautions concerning working environment and conditions

3.1 Working environment and working conditions

This equipment, based on the assumption that it is used in the pollution degree 2

 

(Note 1) environment.If it is used in other degree of contamination, 

please do the protection on the device side to be incorporated.Measurement categories for measuring circuit for this equipment is CAT

(Note 1). 

The overvoltage category of the auxiliary power supply circuit (MA, MB) is CAT

(Note 1).Do not use the unit in any of the following places. Doing so 

may cause malfunction or reduction in service life.

Place where the ambient temperature exceeds the working temperature range(

5

°

C -

+55

°

C)

Place where the humidity exceeds the humidity range (30% - 85%RH) or 

condensation occurs

Place with much dust, corrosive gas, salt or oily smoke

Place where the unit may be exposed to rain or drops of water

Place where metallic particles or inductive substances are dispersed

Place where the daily mean temperature exceeds 35

°

C

Place with much vibration or impact

Place exposed to direct sunlight

Place with strong electromagnetic field or much foreign noise

Place where the altitude is over 2000m

This equipment is the open type equipment. (Electric shock protection of the instrument was designed to perform housed in another apparatus 

equipment) Please use are housed in a control panel etc. Always. For notes on when to adapt the equipment that you have configured in this 

equipment to the EMC Directive, please refer to the Instruction Manual (Detail edition).

Note 1

For a definition of pollution degree and the measurement categories, please refer to the EN61010-1 / 2010.

3.2 Preparation before using 

An installation place should keep the working environment and working conditions.

The protection sheet for the crack prevention is put on the display part. Before use 

this product, remove the protection sheet. It is not unusual, although a LCD display 

part may light up by generating of static electricity in case it removes. After a while,

it disappears by natural electric discharge.

 

Following setup is need before using EMU4-D65.

   

The one always in one system is the Master set, Other display unit of, please to Slave configuration.

(The wrong setting and it does not work)

3.3 Installation and connection 

Before installing and connecting the unit, read the instruction manual without fail. For safety, the unit shall be installed and connected by experts in electrical work.

When threading and wiring, take utmost care that cuttings and wire pieces do not enter the unit.

Connect the wires carefully checking the wiring diagram. Improper wiring can cause unit failure, fire and electric shock.

Perform wiring work in a dead state. Do not wire the unit in a live state. Doing so can cause electric shock, ground fault, unit failure and fire.

3.4 Precautions for Use 

This unit cannot be used for deal and proof of electric energy measurement stipulated in Measurement Act.

Use this unit within the ratings specified in this manual. If it is used outside the ratings, it may cause not only malfunction or failure but also fire burnout.

Do not disassemble or modify this unit. It may cause failure, malfunction, injury or fire.

Do not touch the live part such as connection terminal. It may cause electric shock, electric burn injury or burnout of the device. If any exposed conductor is found, stop the operation 

immediately, and take an appropriate action such as isolation protection.

 

3.5 Maintenance Precautions

Use a soft dry cloth to clean off dirt of the unit surface. Do not let a chemical cloth remain on the surface for an extended period of time nor wipe the surface with thinner 

or benzene.

Check for the following items to use this unit properly for long time.

(1) Daily maintenance

(a) No damage on this unit

(b) No abnormality with LED

(c) No abnormal noise, smell or heat

(2) Periodical maintenance (Once every 6 months to 1 year)

No looseness with installation and wire connection

Do periodical maintenance under the electric outage condition. Failure to do so may cause electric shock, failure of the unit or a fire. Tighten the terminal regularly to prevent a fire. In case 

a display unit is attached to a sensor unit, get off the display unit during maintaining or tightening terminals.

3.6 Storage Precautions

To store this unit, turn off the power and remove wires, and put it in a plastic bag.

For long-time storage, avoid the following places. Failure to follow the instruction may cause a failure and reduced life of the unit.

Places the Ambient temperature exceeds the range -10°C - +60°C.

Places the Relative humidity exceeds the range 30% - 85% or places with dewfall.

Dust, corrosive gas, saline and oil smoke exist.

Places the average daily temperature exceeds 35°C.

Vibration and impact exceed the specifications.

Places exposed to rain, water drop or direct sunlight.

Places metal fragments or conductive substance are flying.

This  product  is  the  optional 

dedicated  product  only  for 

Mitsubishi Energy Measuring Unit 

(EcoMonitorPlus, EcoMonitorPro) 

and Mitsubishi Measuring Unit for 

MDU  Breakers (MDU2).  It  can  not 

be used for other purpose.

Please use after removing the 

protection sheet.

 

EMU4-D65

Caution

Caution

Caution

EMU4-PX4 and 

EMU4-AX4 is supported with later version 2.00. For information about how to determine the version, please refer to 7.2.7.

Summary of Contents for EMU4-D65

Page 1: ...ollowing setup is need before using EMU4 D65 The one always in one system is the Master set Other display unit of please to Slave configuration The wrong setting and it does not work 3 3 Installation and connection Before installing and connecting the unit read the instruction manual without fail For safety the unit shall be installed and connected by experts in electrical work When threading and ...

Page 2: ...uit LED A circuit number on display lights up Moreover LED of the circuit number blinks at the time of alarm occuring OUT 1 Connector Use for connection with a next display unit OUT 2 Connector Use for connection with a next display unit IEC rail attachment Use when installating on IEC rail Master LED The light is switched on at the time of operation key Change of display item and selection of a m...

Page 3: ...antaneous power failure alarm Setup for the condition of monitoring breaker alarm Monitoring for measurement data Please refer to the instruction manual Detailed edition Please refer to the instruction manual Detailed edition Reset the Max Min data and alarm data Preset the value of Wh and varh Setup Setup Reset Set Connection test Pulse output test Alarm output test Communication test Test mode i...

Page 4: ...key and change the set value 2 Push the Phase key and confirm the setting value 3 3 6 will be displayed 3 6 1 Push the key and change the set value 2 Push the Phase key and confirm the setting value 3 3 1 will be displayed 4 Setup the primary current All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 4 1 1 In 4 1 Push the and move the cursor to the 3 A rate 2 Push the Phase key 3 4 2 will be ...

Page 5: ...ate UNB V Voltage unbalance rate HA Harmonics current HV Harmonics voltage 5 4 1 Push the or key and change the HA HV value 2 Push the Phase key 3 5 1 will be displayed HA HV r m s In case of the model EMU4 BM1 MB HA HV can not be set r m s to display the RMS value of harmonic current or harmonic voltage The not be displayed to display the distortion rate and content rate of harmonic current or ha...

Page 6: ...ase key and confirm the setting value 3 9 1 will be displayed 10 Setup the Simple measurement All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 10 1 1 In 10 1 push the or key and move the cursor to the 9 SimpleMEA 2 Push the Phase key 3 10 2 will be displayed 10 2 1 Push the or key and select SimpleMEA On Off 2 Push the Phase key and confirm the setting value 3 Transition to the following sc...

Page 7: ...ush the key and change the number of moving average 2 Push the Phase key and confirm the setting value 3 12 9 will be displayed 12 9 1 Push the key and change the upper limit lower limit and unit 2 Push the Phase key and confirm the setting value 3 12 10 will be displayed 12 10 1 Push the or key and select the AD converted On Off 2 Push the Phase key and confirm the setting value 3 Transition to t...

Page 8: ...ill be displayed 13 2 4 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 5 will be displayed 13 2 5 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 1 will be displayed 14 Save the settings 14 1 14 2 1 After setting all of the items and push the Setup key 2 14 1 will be displayed 3 When save the settings push the or ...

Page 9: ...setting To 2 6 Contact setting To 2 7 2 6 1 Push the key and change the CONV Rate value and unit 2 Push the Phase key and confirm the setting value 3 2 8 will be displayed 2 7 1 Push the or key and select thereset mode 2 Push the Phase key 3 2 8 will be displayed 2 8 1 Push the or key and select the input method Non Contact Pulse 2 Push the Phase key 3 Transition to the following screen by the set...

Page 10: ...tput EMU4 HM1 MB EMU4 A2 EMU4 VA2 EMU4 PX4 EMU4 AX4 I O 1 Input 2 OP Time 3 Output OP Time Off 1 OP Time Mode A 1 OP Time Off 2 OP Time Mode A 2 Model EMU4 PX4 or 2 circuits measuring only 2 circuits measuring only OP Time Off 3 OP Time Off 4 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Output 2 Push the Phase key 3 4 2 will be displayed EMU4 HM1 MB EMU4 A2 EMU4 VA2 Output Non Pulse A...

Page 11: ...1 MB EMU4 LG1 MB 3 1 1 In 3 1 Push the or key and move the cursor to the 2 Baut rate 2 Push the Phase key 3 3 2 will be displayed Baut rate 2400 4800 9600 19200 38400 3 2 1 Push the or key and select the baut rate 2 Push the Phase key 3 3 1 will be displayed 4 Setup the parity EMU4 BM1 MB EMU4 HM1 MB EMU4 LG1 MB 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Parity 2 Push the Phase key ...

Page 12: ...ng all of the items push the or key and move the cursor to the OK 7 Push the Phase key and clock setting changed Note 2 8 2 2 will be displayed 9 When to exit the clock setup push the or key and move the cursor to the OK and push the Phase key If select the Cancel return to 1 1 10 After completing the settings saving and 1 1 will be displayed Year 00 01 02 13 99 Month 01 02 03 04 12 Day 01 02 29 3...

Page 13: ...ring 2 Push the Phase key 3 2 2 will be displayed Wiring 1P2W 1P3W 3P3W 3P4W 3P4W setting is EMU2 RD 4W only 3P4W fixed 2 4 C In the case of the model MDU2 displays all 1P2W 3P4W but can not be set for 3P4W in the case of connection breaker 3 pole products 2 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 2 1 will be displayed 3 Setup the primary v...

Page 14: ...2kW Wfull 120kW 0 01 0 1 1 10 120kW Wfull 1200kW 0 1 1 10 100 1200kW Wfull 12000kW 1 10 100 1000 12000kW Wfull 120000kW 10 100 1000 10000 120000kW Wfull 100 1000 10000 100000 7 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 7 1 will be displayed 8 Setup 1 3Change MDU2 8 1 1 In 8 1 Push the or key and move the cursor to the 7 1 3Change 2 Push the P...

Page 15: ...ote 1 Transition to the setup mode 1 1 1 Push the Setup key in operation mode 2 1 1 will be displayed 1 In 1 1 Push the or key and move the cursor to the 3 Display 2 Push the Phase key 3 2 1 will be displayed 2 Setup the LCD contrast 2 1 1 Push the or key and move the cursor to the 1 Contrast 2 Push the Phase key 3 2 2 will be displayed Contrast 2 2 1 Push the or key and change the LCD contrast va...

Page 16: ... for between the display unit connection Model EMU2 CB1 DP 10 Warranty If you have any questions or the product is broken down contact our sales representative near you The charge free warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing Repair shall be charged for the case failures occur due to your intent or fault even during the char...

Reviews: