- 9 -

Screen

Operation

Note

2 Setup input 

EMU4-HM1-MB, EMU4-PX4

2-1.

 

 

 
 

1

In 2-1,

 

Push the   

    or   

    key

 

, and move the cursor to the ”1 Input”.

2

Push the

   

    / Phase    key.

3

2-2 will be displayed.

 

2-2.

 

 

 
 

1

Push the   

    or   

    key

 

, and select the input method.

(Non/

 

Contact /Pulse)

2

Push the

   

    / Phase    key.

3

Transition to the following screen by the model and setting input method.

[Non] setting

Model

EMU4-HM1-MB 

 To 2-1

Model

EMU4-PX4

 To 2-5

[Pulse] setting

 To 2-3

[Contact] setting

 To 2-4

[CONV.Rate]

0.001

10000

1.000

[Unit]

Non

Wh

kWh

MWh

2

3

kL

sec

min

hour

kg

 

[ResetMode]

Auto

Hold

 

 

Auto…Contact input state is reset automaticaly when

contact input is less.

Hold…Contact input state is hold until contact input 

released even thought contact input is less.

(For  information about  how  to  release  of  the 

contact  input,  please  refer  to  the  instruction 

manual (Detailed edition))

2-3.

 

 

 
 

1

Push the

   

   

   

key,

 

and change the “CONV.Rate” value 

and unit.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

Transition to the following screen by the model.

Model

EMU4-HM1-MB 

To 2-1

Model

EMU4-PX4 

To 2-5

2-4.

 

 

 
 
 
 

1

Push the   

    or   

key, and select thereset mode.

2

Push the

   

    / Phase    key.

3

Transition to the following screen by the model.

Model

EMU4-HM1-MB 

To 2-1

Model

EMU4-PX4 

To 2-5

2-5.

1

Push the   

or   

key

 

, and select the input method.

(Non/

 

Contact /Pulse)

2

Push the

   

    / Phase    key.

3

Transition to the following screen by the setting input method.

[Non] setting

 To 2-8

[Pulse] setting

 To 2-6

[Contact] setting

 To 2-7

2-6.

1

Push the

   

   

   

    key,

 

and change the “CONV.Rate” value 

and unit.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

2-8 will be displayed.

2-7.

1

Push the   

or   

key, and select thereset mode.

2

Push the

   

    / Phase    key.

3

2-8 will be displayed.

2-8.

1

Push the   

    or   

    key

 

, and select the input method.

(Non/

 

Contact /Pulse)

2

Push the

   

    / Phase    key.

3

Transition to the following screen by the setting input method.

[Non] setting

 To 2-11

[Pulse] setting

 To 2-9

[Contact] setting

 To 2-10

2-9.

1

Push the

   

   

   

    key,

 

and change the “CONV.Rate” value 

and unit.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

2-11 will be displayed.

2-10.

1

Push the   

or   

key, and select thereset mode.

2

Push the

   

    / Phase    key.

3

2-11 will be displayed.

2-11.

1

Push the   

or   

key

 

, and select the input method.

(Non/

 

Contact /Pulse)

2

Push the

   

    / Phase    key.

3

Transition to the following screen by the setting input method.

[Non] setting

 To 2-1

[Pulse] setting

 To 2-12

[Contact] setting

 To 2-13

2-12.

1

Push the

   

   

   

    key,

 

and change the “CONV.Rate” value 

and unit.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

2-1 will be displayed.

2-13.

1

Push the   

or   

key, and select thereset mode.

2

Push the

   

    / Phase    key.

3

2-1 will be displayed.

[I/O]

1

 

Input

2

 

OP.Time

3

 

Output

[ResetMode]

Auto

[2]

[CONV.Rate]

1

.000

[Unit]

Non             

[2]

[Input]

Non

[2]

[CONV.Rate]

1

.000

[Unit]

Non             

[3]

[Input]

Non

[3]

[ResetMode]

Auto

[3]

[CONV.Rate]

1

.000

[Unit]

Non             

[4]

[Input]

Non

[4]

[ResetMode]

Auto

[4]

[ResetMode]

Auto

[1]

[CONV.Rate]

1

.000

[Unit]

Non             

[1]

[Input]

Non

[1]

EMU4-PX4 only

EMU4-PX4 only

EMU4-PX4 only

[CONV.Rate]

1

.000

[Unit]

Non             

[1]

[Input]

Non

[1]

[ResetMode]

Auto

[1]

<EMU4-HM1-MB>

[Input]

Non

Contact

Pulse

<EMU4-PX4>

[Input]

Pulse

Contact

Non

 

Summary of Contents for EMU4-D65

Page 1: ...ollowing setup is need before using EMU4 D65 The one always in one system is the Master set Other display unit of please to Slave configuration The wrong setting and it does not work 3 3 Installation and connection Before installing and connecting the unit read the instruction manual without fail For safety the unit shall be installed and connected by experts in electrical work When threading and ...

Page 2: ...uit LED A circuit number on display lights up Moreover LED of the circuit number blinks at the time of alarm occuring OUT 1 Connector Use for connection with a next display unit OUT 2 Connector Use for connection with a next display unit IEC rail attachment Use when installating on IEC rail Master LED The light is switched on at the time of operation key Change of display item and selection of a m...

Page 3: ...antaneous power failure alarm Setup for the condition of monitoring breaker alarm Monitoring for measurement data Please refer to the instruction manual Detailed edition Please refer to the instruction manual Detailed edition Reset the Max Min data and alarm data Preset the value of Wh and varh Setup Setup Reset Set Connection test Pulse output test Alarm output test Communication test Test mode i...

Page 4: ...key and change the set value 2 Push the Phase key and confirm the setting value 3 3 6 will be displayed 3 6 1 Push the key and change the set value 2 Push the Phase key and confirm the setting value 3 3 1 will be displayed 4 Setup the primary current All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 4 1 1 In 4 1 Push the and move the cursor to the 3 A rate 2 Push the Phase key 3 4 2 will be ...

Page 5: ...ate UNB V Voltage unbalance rate HA Harmonics current HV Harmonics voltage 5 4 1 Push the or key and change the HA HV value 2 Push the Phase key 3 5 1 will be displayed HA HV r m s In case of the model EMU4 BM1 MB HA HV can not be set r m s to display the RMS value of harmonic current or harmonic voltage The not be displayed to display the distortion rate and content rate of harmonic current or ha...

Page 6: ...ase key and confirm the setting value 3 9 1 will be displayed 10 Setup the Simple measurement All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 10 1 1 In 10 1 push the or key and move the cursor to the 9 SimpleMEA 2 Push the Phase key 3 10 2 will be displayed 10 2 1 Push the or key and select SimpleMEA On Off 2 Push the Phase key and confirm the setting value 3 Transition to the following sc...

Page 7: ...ush the key and change the number of moving average 2 Push the Phase key and confirm the setting value 3 12 9 will be displayed 12 9 1 Push the key and change the upper limit lower limit and unit 2 Push the Phase key and confirm the setting value 3 12 10 will be displayed 12 10 1 Push the or key and select the AD converted On Off 2 Push the Phase key and confirm the setting value 3 Transition to t...

Page 8: ...ill be displayed 13 2 4 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 5 will be displayed 13 2 5 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 1 will be displayed 14 Save the settings 14 1 14 2 1 After setting all of the items and push the Setup key 2 14 1 will be displayed 3 When save the settings push the or ...

Page 9: ...setting To 2 6 Contact setting To 2 7 2 6 1 Push the key and change the CONV Rate value and unit 2 Push the Phase key and confirm the setting value 3 2 8 will be displayed 2 7 1 Push the or key and select thereset mode 2 Push the Phase key 3 2 8 will be displayed 2 8 1 Push the or key and select the input method Non Contact Pulse 2 Push the Phase key 3 Transition to the following screen by the set...

Page 10: ...tput EMU4 HM1 MB EMU4 A2 EMU4 VA2 EMU4 PX4 EMU4 AX4 I O 1 Input 2 OP Time 3 Output OP Time Off 1 OP Time Mode A 1 OP Time Off 2 OP Time Mode A 2 Model EMU4 PX4 or 2 circuits measuring only 2 circuits measuring only OP Time Off 3 OP Time Off 4 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Output 2 Push the Phase key 3 4 2 will be displayed EMU4 HM1 MB EMU4 A2 EMU4 VA2 Output Non Pulse A...

Page 11: ...1 MB EMU4 LG1 MB 3 1 1 In 3 1 Push the or key and move the cursor to the 2 Baut rate 2 Push the Phase key 3 3 2 will be displayed Baut rate 2400 4800 9600 19200 38400 3 2 1 Push the or key and select the baut rate 2 Push the Phase key 3 3 1 will be displayed 4 Setup the parity EMU4 BM1 MB EMU4 HM1 MB EMU4 LG1 MB 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Parity 2 Push the Phase key ...

Page 12: ...ng all of the items push the or key and move the cursor to the OK 7 Push the Phase key and clock setting changed Note 2 8 2 2 will be displayed 9 When to exit the clock setup push the or key and move the cursor to the OK and push the Phase key If select the Cancel return to 1 1 10 After completing the settings saving and 1 1 will be displayed Year 00 01 02 13 99 Month 01 02 03 04 12 Day 01 02 29 3...

Page 13: ...ring 2 Push the Phase key 3 2 2 will be displayed Wiring 1P2W 1P3W 3P3W 3P4W 3P4W setting is EMU2 RD 4W only 3P4W fixed 2 4 C In the case of the model MDU2 displays all 1P2W 3P4W but can not be set for 3P4W in the case of connection breaker 3 pole products 2 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 2 1 will be displayed 3 Setup the primary v...

Page 14: ...2kW Wfull 120kW 0 01 0 1 1 10 120kW Wfull 1200kW 0 1 1 10 100 1200kW Wfull 12000kW 1 10 100 1000 12000kW Wfull 120000kW 10 100 1000 10000 120000kW Wfull 100 1000 10000 100000 7 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 7 1 will be displayed 8 Setup 1 3Change MDU2 8 1 1 In 8 1 Push the or key and move the cursor to the 7 1 3Change 2 Push the P...

Page 15: ...ote 1 Transition to the setup mode 1 1 1 Push the Setup key in operation mode 2 1 1 will be displayed 1 In 1 1 Push the or key and move the cursor to the 3 Display 2 Push the Phase key 3 2 1 will be displayed 2 Setup the LCD contrast 2 1 1 Push the or key and move the cursor to the 1 Contrast 2 Push the Phase key 3 2 2 will be displayed Contrast 2 2 1 Push the or key and change the LCD contrast va...

Page 16: ... for between the display unit connection Model EMU2 CB1 DP 10 Warranty If you have any questions or the product is broken down contact our sales representative near you The charge free warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing Repair shall be charged for the case failures occur due to your intent or fault even during the char...

Reviews: