9-8. FUNCTION OF SWITCHES
PUHZ-W50VHA(-BS) PUHZ-W85VHA(-BS)
PUHZ-W50VHAR1(-BS) PUHZ-W85VHAR1(-BS)
PUHZ-W50VHAR2(-BS)
PUHZ-W50VHAR3(-BS)
Switch
Function
Selection
Default
setting
Function details
Effective timing
(SW1, 8)/
Note (SW6)
Mark No.
ON (with)
OFF (without)
SW1
1
Manual
defrost
ON to start
Usual setting
OFF
Switch ON to force defrosting
When compressor
is working in
heating mode.
*1
2
To clear error
history
ON to clear
Usual setting
OFF
Switch ON to clear (erase) the
following:
(1) Check codes and Suspension
flags in RAM
(2) Check codes and Suspension
flags in EEPROM
Off or operating
3
No function
Do NOT use
PUHZ-W50,85VHA
OFF
–
–
4
No function
Do NOT use
PUHZ-W50,85VHA
OFF
5
No function
Do NOT use
PUHZ-W50,85VHA
OFF
6
No function
Do NOT use
PUHZ-W50,85VHA
OFF
SW5
1
Max. fan step
selection
STEP 9
STEP 8
OFF
Selection of max. fan step at the
silent mode
Always
2 Max. frequency
selection
Middle level
Low level
OFF
Selection of max. compressor
frequency at the silent mode
Always
3
No function
Do NOT use
PUHZ-W50,85VHA
OFF
–
–
4 Model setting 3
–
–
Refer to the
table of SW6
SW6
1 Model Setting 1
Do NOT use
PUHZ-W50,85VHA
OFF
PCB may be damaged, if switch is
ON.
ON for other models
2
Defrost control
selection
For high humidity
Standard
OFF
Switches to optimal defrosting
operation for low-temperature and
high-humidity regions.
–
3–6
Model Setting 2
As shown in
the left table
–
Make sure to set
SW6-3 to 6 and
SW10-1,2 correctly
SW10 1,2
SW8
1
Mode selection
Energy saving
mode
Powerful mode
OFF
–
Always
2
No function
Do NOT use
PUHZ-W50,85VHA
OFF
–
–
3
Separate
Interface/Flow
temp. controller-
outdoor unit
power supplies
Separate power
supply
Outdoor unit power
supply
OFF
Power supply connection method
selection
When power supply
ON
<Important Note>
All these DIP switches on PUHZ-W50,85VHA are set as shown above.
Spare PCBs, however, will be supplied without any settings, which means that all DIP switches are switched OFF.
When servicing, please make sure to set all switches correctly, referring to the previous PCB which is removed from the unit.
*1
. Manual defrost should be done as follows.
1
Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2
Manual defrost will start by the above operation
1
if these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor starts operating or previous manual defrost is finished.
• Pipe temperature is less than or equal to 8
:
.
Manual defrost will finish if certain conditions have been satisfied.
Manual defrost can be done if above conditions have been satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again.
This depends on the service conditions.
Model
SW5
SW6
SW10
4
3
4
5
6
1
2
W50VHA
W50VHAR1 0
1
1
0
0
0
1
W50VHAR2
W50VHAR3 1
1
1
0
0
0
1
W85VHA
0
1
0
1
0
0
0
W85VHAR1 0
1
0
1
0
0
1
1=ON, 0=OFF