93
OCH439M
Comp. surface temperature (TH33)
(for W50VHA(R1,R2,R3)/W85VHAR1)
Comp. surface temperature (TH34)
(for HW
•
HA2R3–R7)
3 to 217
1
ON
2 3 4 5 6
Code
display
1
ON
2 3 4 5 6
Requested capacity step (Q STEP)
0 to 7
0 to 7
Step
SW2 setting
Display detail
Explanation for display
Unit
LEV-C opening pulse (for HW112/140)
0 to 500
0 to 500
(When it is 100 pulse or more, hundreds digit are
displayed by turns.)
1
ON
2 3 4 5 6
:
:
3 to 217
(When the temperature is 100
:
or more, the
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 130
:
;
0.5 s 0.5 s 2 s
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoor suction pipe temperature (TH33)
(for HW112/140) −39 to 88
:
1
30
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 s 0.5 s 2 s
15
The black square (
■
) indicates a switch position.
Normal
Overvoltage error
Undervoltage error
Input current sensor error
L
1
-phase open error
Abnormal power synchronous signal
PFC error (W50V)
(Overvoltage/Undervoltage/Overcurrent)
PFC/ATCM/IGBT error (W50–85V/HW140V)
Undervoltage
• Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
L
1
phase open error (04) + PFC/ATCM/IGBT error (20) = 24
Description
Display
00
01
02
04
08
10
20
U9 error details (To be shown while