OPERATING PROCEDURE
PHOTOS/FIGURES
14. Removing the reactors (ACL1, ACL2, ACL3)
(PUHZ-HW112/140Y)
(1)
Remove the service panel. (See Photo 1)
(2)
Remove the top panel. (See Photo 1)
(3)
Remove the 6 screws, that fix the front panel and remove
the front panel.
(4)
Remove the 2 screws, screw
8
and
9
(both 4 × 10), that
fix the separator, screw
8
from the stay and screw
9
from the bottom of the separator, and tilt the separator to
the side of the fan motor slightly. (See Photo 20)
(5)
Disconnect the lead wires from the reactor and remove
the 4 screws, screw
0
, that fix the reactor to remove the
reactor. (See Photo 21 and 22)
Note 1: The reactor is very heavy (4 kg)!
Be careful when handling it.
Note 2: The reactor box is also removable.
Photo 20
Photo 22
Photo 21
Reactors
Reactor box
Propeller
Screw
8
Stay
Screw
9
Reactor box
Electrical parts box
Screw
0
Reactor box
118