68
OCH439M
9-6. TEST POINT DIAGRAM
Outdoor controller circuit board
PUHZ-W50VHA(-BS)
PUHZ-W85VHA(-BS)
PUHZ-W50VHAR1(-BS) PUHZ-W85VHAR1(-BS)
PUHZ-W50VHAR2(-BS)
PUHZ-W50VHAR3(-BS)
CNS
S1-S2: 230 V AC
CNAC
2
–
4
: Power supply for
outdoor controller circuit
board
(230 V AC)
1
–
3
:
Power supply for inter-
face unit/Flow temp.
controller-outdoor unit
connection wire
(230 V AC)
CN2
Connect to the outdoor
power circuit board (CN2).
1
–
5
:
Power circuit board
Transmitting signal to the
controller circuit board
(0–5 V DC)
2
–
5
: Zero cross signal
(0–5 V DC)
3
–
4
: Not used (W50)
18 V DC (W85)
6
–
5
: 16 V DC
7
–
5
: 16 V DC
21S4
4-way valve
63H
High pres-
sure switch
SV2
Bypass valve
CN4
Transmission to outdoor
power circuit board (CN4)
SW6
Model select
SW1
Manual defrost,
detect history record
reset
TH4
Thermistor
<Discharge>
TH3
Thermistor
<Liquid>
TH7
Thermistor
<Ambient>
TH6
Thermistor
<Plate Hex liquid>
CNDC
280–380 V DC
Connect from outdoor
power circuit board.
–
+
}
V
CC
(TEST POINT
2
)
(voltage between pins of
C6B): 15 V DC
V
DC
(TEST POINT
1
)
(voltage between pins of C5E):
280–330 V DC
V
FG
(voltage between right
pins of PC5D, pin 3
and pin 4)
V
SP
(voltage between pins
of C5B): 0 V DC (when
stopped), 1–6.5 V
(when operated)
<CAUTION> TEST POINT
1
is high voltage.
SW10
Model select
LEV-A,-B
Linear expansion valve
CN52C
Connect to the outdoor noise
filter circuit board. (CN52C)
TH32
Thermistor
<Inlet water>
SW8
Function switch
SW2
Operation monitor
function
SW5
Function switch
–
+
Communication
power supply
D71 Voltage
24 V DC
TH33
Thermistor
(W50VHA(R1,R2), W85VHAR1)
<Comp. surface>
CNDM
1
–
2
:Input of low level
sound priority mode
SV1
Drain hose heater output
1
,
2
,
6
,
7
: +
5
: –
]
[