1
. Multiple outdoor units control
L
N
S3
S2
S1
<Fig. .3.3>
.3.2 Slave unit
Connect each outdoor unit to a slave unit.
FTC4 (Slave) can be powered in two ways.
1. Power cable is run from the outdoor unit to a slave unit.
2. FTC (Slave) has indipendent power source.
FTC4 (Master) (PAC-IF051B-E) used as slave
• For wiring as a slave controller, refer to "4.1 Electrical connection". *1
*1 Don't connect the power cable to the booster heater because it doesn't work in
slave controller setting.
FTC4 (Slave) (PAC-SIF051B-E) <Fig. .3.3>
FTC4 (Slave) can be powered in two ways.
1. Power cable is run from the outdoor unit to FTC4 (Slave).
2. FTC4 (Slave) has independent power source
Note:
•
Do not run the low voltage cables through a slot that the high voltage
cables go through.
•
Bundle cables by using clamps as shown in the figure to the right .
Low voltage cables (INPUT) &
Thermistor cables
High voltage cables (OUTPUT) &
Power cables
Wiring
Wiring No.
× size
(mm²)
FTC4 (Slave) - Outdoor unit
*2
3 × 1.5 (polar)
FTC4 (Slave) - Outdoor unit earth
*2
1 × Min. 1.5
Circuit
rating
FTC4 (Slave) - Outdoor unit S1 - S2
*3
230V AC
FTC4 (Slave) - Outdoor unit S2 - S3
*3
24V DC
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*2. Max. 45 m
If 2.5 mm² used, Max. 50 m
If 2.5 mm² used and S3 separated, Max. 80 m
*3. The values given in the table above are not always measured against the ground value.
Notes:
1. Wiring size must comply with the applicable local and national codes.
2. FTC4 (Slave)/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
FTC4 (Slave) power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
Power
supply
~/N
230V
50Hz
Earth
leakage
circuit
breaker
*1
Wiring
circuit
breaker
or
Isolating
switch
L
N
S1
S2
S3
Outdoor unit
S1
S2
S3
TB6
TB6
FTC4 (Slave)
L
N
Power
supply
3N~
400V
50Hz
Earth
leakage
circuit
breaker
*1
Wiring
circuit
breaker
or
Isolating
switch
L3
L2
L1
N
S1
S2
S3
Outdoor unit
S1
S2
S3
FTC4 (Slave)
L
N
<1 phase>
Option 1: FTC4 (Slave) powered via outdoor unit
*1 If the installed earth leakage circuit breaker does not have an over-current protection function, install a breaker with that function along the same power line.
Note: In accordance with IEE regulations the circuit breaker/isolating switch located on the outdoor unit should be installed with lockable devices (health and safety).
<Fig. .3.4>