5.1 DIP Switch Functions
The DIP switch number is printed on the circuit board next to the relevant switch-
es. The word ON is printed on the circuit board and on the DIP switch block itself.
To move the switch you will need to use a pin or the corner of a thin metal ruler or
similar.
DIP switch settings are listed below in Table 5.1.1.
Only an authorised installer can change DIP switch setting under one’s own re-
sponsibility according to the installation condition.
Make sure to turn off both indoor unit and outdoor unit power supplies before
changing the switch settings.
DIP switch
Function
OFF
ON
Default settings
SW1 SW1-1
—
—
—
OFF
SW1-2
—
—
—
OFF
SW1-3
—
—
—
OFF
SW1-4
—
—
—
OFF
SW1-5 Booster heater
WITHOUT Booster heater
WITH Booster heater
ON
SW1-6
—
—
—
ON
SW1-7 Outdoor unit type
Split type
Packaged type
OFF
SW1-8
—
—
—
OFF
SW2 SW2-1 Room thermostat1 input (IN1) logic change
Operation stop at thermostat short
Operation stop at thermostat open
OFF
SW2-2
—
—
—
OFF
SW2-3 Booster heater capacity restriction
Inactive
Active
ON *1
SW2-4
—
—
—
OFF
SW2-5 Automatic switch to backup heat source operation
(When outdoor unit stops by error)
Inactive
Active *2
OFF
SW2-6
—
—
—
OFF
SW2-7
—
—
—
OFF
SW2-8 Flow sensor
WITHOUT Flow sensor
WITH Flow sensor
ON
SW3 SW3-1
—
—
—
OFF
SW3-2
—
—
—
OFF
SW3-3
—
—
—
OFF
SW3-4 Electric energy meter
WITHOUT Electric energy meter
WITH Electric energy meter
OFF
SW3-5
—
—
—
ON
SW3-6
—
—
—
OFF
SW3-7
—
—
—
OFF
SW3-8 Heat meter
WITHOUT Heat meter
WITH Heat meter
OFF
SW4 SW4-1
—
—
—
OFF
SW4-2
—
—
—
OFF
SW4-3
—
—
—
OFF
SW4-4 Indoor unit only operation (during installation work) *3
Inactive
Active
OFF
SW4-5 Emergency mode (Heater only operation)
Normal
Emergency mode (Heater only operation) OFF *4
SW4-6
—
—
—
OFF
SW5 SW5-1
—
—
—
OFF
SW5-2 Advanced auto adaptation
Inactive
Active
ON
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
SW5-8
—
—
—
OFF
SW6 SW6-1
—
—
—
OFF
SW6-2
—
—
—
OFF
SW6-3
—
—
—
OFF
SW6-4 Analog output
Inactive
Active
OFF
SW6-5
—
—
—
OFF
<Table 5.1.1>
<Figure 5.1.1>
SW1
SW3
SW4
SW2
SW5
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
EHSC-VM6D-CN
ON
ON
ON
ON
OFF
Capacity code
SW6
Note:
*1 The switch must be turned OFF when the maximum output of heater (5.5 kW) is necessary.
*2. OUT11 will be available. For safety reasons, this function is not available for certain errors. (In that case, system operation must be stopped and only
the water circulation pump keeps running.)
*3. Space heating can be operated only in indoor unit, like an electric heater. (Refer to “5.3 Indoor unit only operation”. )
*4. If emergency mode is no longer required, return the switch to OFF position.