Service and Maintenance
en
Engineers Forms
Should settings be changed from default, please enter and record new setting in ‘Field Setting’ column. This will ease resetting in the future should the system use change
or the circuit board need to be replaced.
Commissioning/Field settings record sheet
Main remote controller screen
Parameters
Default setting
Field
setting Notes
Main
Heating room temp.
10°C - 30°C
20°C
Heating flow temp.
20°C - 60°C
45°C
Heating compensation curve
−9°C - + 9°C
0°C
Holiday mode
Active/Non active/Set time
—
Option
Heating
On/Off/Timer
On
Energy monitor
Consumed electrical energy/Delivered energy
—
Setting
Heating
Operation mode
Heating room temp./ Heating flow temp./ Heating com
-
pensation curve
Room temp.
Compensation
curve
Hi flow temp. set
point
Outdoor ambient temp.
−30°C - +33°C
*1
−15°C
Flow temp.
20°C - 60°C
50°C
Lo flow temp. set
point
Outdoor ambient temp.
−28°C - +35°C
*2
35°C
Flow temp.
20°C - 60°C
25°C
Adjust
Outdoor ambient temp.
−29°C - +34°C
*3
—
Flow temp.
20°C - 60°C
—
Holiday
Heating
Active/Non active
Active
Heating room temp.
10°C - 30°C
15°C
Heating flow temp.
20°C - 60°C
35°C
Initial settings
Language
EN/CN
CN
°C/°F
°C/°F
°C
Summer time
On/Off
Off
Temp. display
Room/Off
Off
Time display
hh:mm/hh:mm AM/AM hh:mm
hh:mm
Room sensor settings for Zone1
TH1/Main RC/“Time/Zone”
TH1
Room RC zone select
Zone1
Zone1
Service menu
Thermistor adjustment
THW1
−10°C - +10°C
0°C
THW2
−10°C - +10°C
0°C
Auxiliary settings
Economy settings for
pump.
On/Off *4
On
Delay (3 - 60 min)
10 min
Electric heater
(Heating)
Space heating: On (used)/Off (not used)
On
Electric heater delay timer (5 - 180 min)
30 min
Flow sensor *5
Minimum(0 - 100L/min)
5 L/min
Maximum(0 - 100L/min)
100 L/min
Analog output
Interval (1 - 30 min)
5 min
Priority(Normal/High)
Normal
Pump speed (Heating)
Pump speed(1 - 5)
5
Heat source setting
Standard/Heater
Standard
Heat pump flow rate range
Minimum(0 - 100L/min)
5 L/min
Maximum(0 - 100L/min)
100 L/min
Operation set-
tings
Heating
operation
Flow temp.range
*6
Min.temp.(20 - 45°C)
30°C
Max.temp.(35 - 60°C)
50°C
Room temp.control
*7
Mode(Normal/Fast)
Normal
Interval(10 - 60min)
10min
Heat pump thermo
diff.adjust
On/Off *4
On
Lower limit(−9 - −1°C)
−5°C
Upper limit(+3 - +5°C)
5°C
Freeze stat function *8
Outdoor ambient temp. (3 - 20°C) / **
5°C
Cold weather function
On/Off *4
Off
Outdoor ambient temp. (−30 - −10°C) *1
−15°C
Floor dry up function
On/Off *4
Off
Target temp.
Start&Finish (20 - 60°C)
30°C
Max. temp. (20 - 60°C)
45°C
Max. temp. period (1 - 20
days)
5 days
Flow temp. (Increase) Temp. increase step (+1 - +10°C)
+5°C
Increase interval (1 - 7 days)
2 days
Flow temp. (De-
crease)
Temp. decrease step (−1 - −
10°C)
−
5°C
Decrease interval (1 - 7 days)
2 days
Summer mode
On/Off
Off
Outdoor ambient
temp.
Heating ON (4-19°C)
10°C
Heating OFF (5-20°C)
15°C
Judgement time
Heating ON (1-48 hours)
6 hours
Heating OFF (1-48 hours)
6 hours
Forced heating ON (-30 - 10°C)
5 °C
(Continued to next page.)