IX
Troubleshooting ]
- 137 -
HWE1417B
GB
Error display/failure condition
Measure/inspection item
[1]
Inverter related errors
4250, 4220, 4230, 4240, 5301, 5114, 0403
Check the details of the inverter error in the error log at maintenance
tool.
Take appropriate measures to the error code and the error details in ac-
cordance with [2] 2.Error code list.
[2]
Main power breaker trip
Refer to "(3) Trouble treatment when the main power breaker is
tripped".(page 140)
[3]
Main power earth leakage breaker trip
Refer to "(4) Trouble treatment when the main power earth leakage
breaker is tripped".(page 140)
[4]
Only the compressor does not operate.
Check the inverter frequency on the LED monitor and proceed to (2) -
[4] if the compressor is in operation.(page 139)
[5]
The compressor vibrates violently at all times or makes an abnor-
mal sound.
See (2)-[4].(page 139)
[6]
Noise is picked up by the peripheral device
<1> Check that power supply wiring of the peripheral device does not
run close to the power supply wiring of the unit.
<2> Check if the inverter output wiring is not running parallel to the
power supply wiring and the transmission lines.
<3> Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<4> Meg failure for electrical system other than the inverter
<5> Attach a ferrite core to the inverter output wiring. (Contact the fac-
tory for details of the service part settings.)
<6> Provide separate power supply to the air conditioner and other
electric appliances.
<7> If the error occurred suddenly, a ground fault of the inverter output
can be considered. See (2)-[4].(page 139)
*Contact the factory for cases other than those listed above.
[7]
Sudden malfunction (as a result of external noise.)
<1> Check that the grounding work is performed properly.
<2>Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<3>Check that neither the transmission line nor the external connec-
tion wiring does not run close to another power supply system or
does not run through the same conduit pipe.
* Contact the factory for cases other than those listed above.
HWE1417B.book 137 ページ 2019年7月16日 火曜日 午後3時47分
Summary of Contents for E Series
Page 1: ......
Page 7: ...vi HWE1417B GB HWE1417B book vi ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 9: ...CONTENTS HWE1417B GB HWE1417B book 2 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 11: ... 2 HWE1417B GB HWE1417B book 2 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 21: ... 12 HWE1417B GB HWE1417B book 12 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 45: ... II Restrictions 36 HWE1417B GB HWE1417B book 36 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 47: ... 38 HWE1417B GB HWE1417B book 38 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 61: ... 52 HWE1417B GB HWE1417B book 52 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 73: ... IV Remote Controller 64 HWE1417B GB HWE1417B book 64 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 75: ... 66 HWE1417B GB HWE1417B book 66 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 83: ... 74 HWE1417B GB HWE1417B book 74 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 87: ... VI Refrigerant Circuit 78 HWE1417B GB HWE1417B book 78 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 89: ... 80 HWE1417B GB HWE1417B book 80 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 115: ... 106 VII Control GB HWE1417B HWE1417B book 106 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 117: ... 108 HWE1417B GB HWE1417B book 108 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 123: ... VIII Test Run Mode 114 HWE1417B GB HWE1417B book 114 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 125: ... 116 HWE1417B GB HWE1417B book 116 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 167: ... 158 HWE1417B GB HWE1417B book 158 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 170: ......