[
IX
Troubleshooting ]
- 121 -
HWE1417B
GB
Problem
Check item
Cause
Solution
The unit has
stopped during
operation and
does not restart.
Automatic Start/Stop
thermistor has tripped.
Water temperature is
high.
Normal
Water temperature is
low.
The setting for the automatic Start/Stop
thermistor is too low.
Change the setting for the automatic Start/
Stop thermistor.
The high-pressure
switch has
tripped.1302, 1303
Water temperature is
not high.
Dirty condenser
Clean the condenser.
Refrigerant overcharge
Evacuate the system, and charge the sys-
tem with refrigerant.
Air in the refrigerant circuit
Evacuate the system, and charge the sys-
tem with refrigerant.
Water flow shortage
Secure enough water flow rate.
The vacuum protection
has tripped.
1301
Outdoor temperature is
not low.
Refrigerant undercharge, refrigerant
gas leakage
Perform a leakage test, repair the leaks,
evacuate the system, and charge the refrig-
erant circuit with refrigerant.
Dirty evaporator
Clean the evaporator.
LEV fault in the main circuit
Replace the LEV in the main circuit.
Clogged strainer
Replace the strainer.
Clogged check valve
Replace the check valve.
Excessive frosting
Install a snow hood to keep snow from ac-
cumulating on the unit.
The discharge
temperature thermistor
has tripped.
1102
Suction gas is
overheated.
Refrigerant undercharge, refrigerant
gas leakage
Perform a leakage test, repair the leaks,
evacuate the system, and charge the refrig-
erant circuit with refrigerant.
LEV fault in the main circuit
Replace the LEV in the main circuit.
Clogged strainer
Replace the strainer.
The cooling fan is stopped.
Check the fan for proper operation, and re-
place it if necessary.
High pressure is too high.
Check the items above and make neces-
sary adjustments so that the suction gas
temperature falls within the specified tem-
perature range.
The unit has
stopped during
operation and
does not restart.
Overcurrent
passed through the
compressor.
4250
Outdoor temperature is
high.
Overload operation
Burnt motor
Seized compressor
Reduce the operation load, and check the
operation patterns.
Replace the compressor.
A water supply cutoff
was detected.
2500, 2501, 2550
The pump is operating
normally.
Water flow shortage
Increase the water flow rate.
Flow switch fault
Replace the flow switch.
The pump does not
operate.
Problem with the solenoid contactor for
the pump
Replace the electromagnetic contactor.
Pump fault
Replace the pump.
The freeze-up
protection function has
tripped.
1503
Water flow shortage
Plate heat exchanger freeze-up
Increase the water flow rate.
The water flow rate is
sufficient.
4-way valve fault
Replace the 4-way valve.
The unit is in
operation, but the
water does not
heat up/cool
down.
Water temperature is
low/high.
The water inlet/outlet
temperature differen-
tial is normal.
The water-heating/cooling load is too
high.
Install more units
Low refrigerant charge due to a leak.
Perform a leakage test, repair the leaks,
evacuate the system, and charge the refrig-
erant circuit with refrigerant.
The water inlet/outlet
temperature differen-
tial is small.
LEV fault in the main circuit
Replace the LEV in the main circuit.
Compressor failure
Replace the compressor.
High pressure is too high, or low pres-
sure is too low.
Operate the units within the specified pres-
sure range.
Water temperature is
high/low.
Water flow shortage
Increase the water flow rate.
Problem with the external devices
Repair the devices.
The unit is mak-
ing a great deal of
vibrations and
noise.
The compressor is
being flooded.
LEV fault in the main circuit
Replace the LEV.
HWE1417B.book 121 ページ 2019年7月16日 火曜日 午後3時47分
Summary of Contents for E Series
Page 1: ......
Page 7: ...vi HWE1417B GB HWE1417B book vi ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 9: ...CONTENTS HWE1417B GB HWE1417B book 2 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 11: ... 2 HWE1417B GB HWE1417B book 2 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 21: ... 12 HWE1417B GB HWE1417B book 12 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 45: ... II Restrictions 36 HWE1417B GB HWE1417B book 36 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 47: ... 38 HWE1417B GB HWE1417B book 38 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 61: ... 52 HWE1417B GB HWE1417B book 52 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 73: ... IV Remote Controller 64 HWE1417B GB HWE1417B book 64 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 75: ... 66 HWE1417B GB HWE1417B book 66 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 83: ... 74 HWE1417B GB HWE1417B book 74 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 87: ... VI Refrigerant Circuit 78 HWE1417B GB HWE1417B book 78 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 89: ... 80 HWE1417B GB HWE1417B book 80 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 115: ... 106 VII Control GB HWE1417B HWE1417B book 106 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 117: ... 108 HWE1417B GB HWE1417B book 108 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 123: ... VIII Test Run Mode 114 HWE1417B GB HWE1417B book 114 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 125: ... 116 HWE1417B GB HWE1417B book 116 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 167: ... 158 HWE1417B GB HWE1417B book 158 ページ 2019年7月16日 火曜日 午後3時47分 ...
Page 170: ......