(2) Connecting the twinning pipe kit

(1) Braze the high-pressure pipe (

6

) to the refrigerant 

service valve.

(2) Screw down the low-pressure twinning pipe kit (

1

) to 

the sheet metal of the refrigerant service valve with the 

screws (

3

), and braze it to the refrigerant service valve.

(3) Braze the elbow (

5

) to the field-piping first, and then 

braze it to the low-pressure twinning pipe kit (

1

).

(4) Braze the elbow (

4

) to the low-pressure pipe in the 

middle.

Note
1. Exercise caution not to burn the cables while brazing the 

pipes.

2. Before brazing pipes to the refrigerant service valve, place 

a wet towel on the valve to keep its temperature from rising 

above 120°C [248°F].

(5) Wrap the u-bend of the low-pressure twinning pipe kit (

1

with the pipe cover (

7

), and tie a band (

c

) around it to 

keep it in place.

(6) Pipe connection (high-pressure side)

· Make sure the pipes from the twinning pipe to the heat source unit are sloped downwards.

· To prevent the refrigerant service valve from being damaged, do 

not let its temperature rise above 120°C [248°F]. 
Place a wet towel on the refrigerant service valve before brazing 
the pipes.

·  Direct  the  blazing  torch  flame  away  from  the  adjacent  cables 

and sheet metal to keep them from being damaged. 

CAUTION

3. Pipe Connection Example

Connect the pipes between heat source units, 
referencing the figure below.

1

Low-pressure 

twinning kit

ID22.2 [7/8] 

-ID25.4 [1]

2

High-pressure twinning pipe

Low-pressure connecting pipe 

(Between heat source units)

Main high-pressure pipe (To BC controller)

Main low-pressure pipe (To BC controller)

Wrap the pipe cover here. 

(Keep out of contact with 

the adjacent sheet metal.)

Field piping  

(Low-pressure connecting pipe: To BC Controller)
Field piping  

(Low-pressure connecting pipe: To heat source unit)

Field piping  

(High-pressure connecting pipe)

1

7c

3

5

4

6

· If high-pressure twinning pipe is installed above the base of the 

heat source unit, it should be no more than 200 mm [7-7/8 in.].

To BC controller

High-pressure twinning pipe

To BC controller

Upward slope

Downslope

200 mm 

[7-7/8 in.]  

max.

To  

indoor unit

High-pressure  

twinning pipe

Heat source unit 2

Heat source unit 1

WT06204X03.indd   3

7/22/2011   1:12:07 PM

Summary of Contents for CMY-Q100CBK

Page 1: ...mponents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room Improper installation may result in refrigerant gas leakage and equipment damage If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer If leaked refrigerant comes in contact with a heat source such as a fan heater stove...

Page 2: ...ning pipe Heat Source unit 1 High pressure c ø15 88 ø19 05 Twinning pipe Heat Source unit 2 Low pressure d ø19 05 ø22 2 Twinning pipe Heat Source unit 2 High pressure e ø15 88 ø19 05 Choose the correct size pipe using the above table Connect the field supplied pipe to the twinning kit for the sizes in the table that are marked with an asterisk Heat source unit 1 Heat source unit 2 To BC controller...

Page 3: ... from being damaged do not let its temperature rise above 120 C 248 F Place a wet towel on the refrigerant service valve before brazing the pipes Direct the blazing torch flame away from the adjacent cables and sheet metal to keep them from being damaged CAUTION 3 Pipe Connection Example Connect the pipes between heat source units referencing the figure below 1Low pressure twinning kit d ID22 2 7 ...

Page 4: ...ver 2High pressure twinning pipe Insulation cover Heat resistant insulation material field supplied Tape field supplied Insulation covers can shrink Overlap the tape as shown in the left figure so that there will be no gap in between the insulation cover or field installed insulation material Overlap margin of the tape 5 Installing the water stopper Make sure to install the supplied water stopper ...

Reviews: