2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit

(1) Pipe size

1

 Field-supply the pipes to be connected to the kit.

2

 If the pipe was cut with a pipe cutter, remove 

the burrs and eliminate foreign materials before 

connecting.

* On the low-pressure side, the twinning kit connects to 

the field-supplied pipes inside the heat source unit. 

The distributor on the low-pressure side must be 

placed in the heat source unit that has a larger 

capacity index of the two, regardless of the relative 

positions of the heat source units or their addresses. 

If the distributor is placed in the heat source unit that 

has a smaller capacity, refrigerant will not be properly 

distributed and compressor failure may result. 

(If heat source units that have the same capacity are 

used in combination, the distributor can be placed in 

either heat source unit.)

Twinning pipe connection size

Package unit name

PQRY-P144

PQRY-P168

PQRY-P192

PQRY-P216

PQRY-P240

Component unit name

Heat Source unit 1

PQRY-P72

PQRY-P96

PQRY-P96

PQRY-P120

PQRY-P120

Heat Source unit 2

PQRY-P72

PQRY-P72

PQRY-P96

PQRY-P96

PQRY-P120

Twinning pipe Kit (optional parts)

CMY-Q100CBK

BC controller~Twinning pipe

High pressure

a

ø22.2

ø28.58

(*)

Low pressure

b

ø28.58

Twinning pipe~Heat Source unit 1 High pressure

c

ø15.88

ø19.05

Twinning pipe~Heat Source unit 2 Low pressure

d

ø19.05

ø22.2

Twinning pipe~Heat Source unit 2 High pressure

e

ø15.88

ø19.05

* Choose the correct size pipe using the above table. Connect the field-supplied pipe to the twinning kit for the sizes in the table that 

are marked with an asterisk (*).

Heat source unit 1

Heat source unit 2

To BC controller

To BC controller

Twinning pipe (high pressure)

1. Confirming the Package Contents

The following items are included with the Twinning Kit (CMY-Q100CBK). Verify that all items are present before starting installation.
* Always use the twinning pipes included in the kit when preparing the twinning kit. 

If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.

(1) Package contents

Model

1

 Low-pressure 

twinning kit

2

 High-pressure 

twinning pipe

3

 Fixing screw

4

 Elbow pipe 

ø22.2 [7/8]

5

 Elbow pipe 

ø28.58 [1-1/8]

6

 High-pressure 

pipe

7

 Pipe cover

CMY-Q100CBK

1

1

1

1

1

1

1

Model

8

 OD19.05 [3/4] 

-ID15.88 [5/8]

9

 OD22.2 [7/8] 

-ID19.05 [3/4]

0

 OD22.2 [7/8] 

-ID25.4 [1]

a

 Installation 

Manual  

(this booklet)

b

 Insulation 

cover

Cable tie

d

 ID22.2 [7/8] 

-ID25.4 [1]

e

 Water stopper

f

 Sealing 

material

CMY-Q100CBK

1

1

1

1

1

2

1

1

1

(2) List of field-supplied parts

· Refrigerant pipes other than the ones provided in the kit.

· Heat-resistant insulation material (for field-supplied refrigerant pipes)

· Insulation cover tape

Twinning kit (low pressure)

 

See reverse.

WT06204X03.indd   2

7/22/2011   1:12:07 PM

Summary of Contents for CMY-Q100CBK

Page 1: ...mponents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room Improper installation may result in refrigerant gas leakage and equipment damage If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer If leaked refrigerant comes in contact with a heat source such as a fan heater stove...

Page 2: ...ning pipe Heat Source unit 1 High pressure c ø15 88 ø19 05 Twinning pipe Heat Source unit 2 Low pressure d ø19 05 ø22 2 Twinning pipe Heat Source unit 2 High pressure e ø15 88 ø19 05 Choose the correct size pipe using the above table Connect the field supplied pipe to the twinning kit for the sizes in the table that are marked with an asterisk Heat source unit 1 Heat source unit 2 To BC controller...

Page 3: ... from being damaged do not let its temperature rise above 120 C 248 F Place a wet towel on the refrigerant service valve before brazing the pipes Direct the blazing torch flame away from the adjacent cables and sheet metal to keep them from being damaged CAUTION 3 Pipe Connection Example Connect the pipes between heat source units referencing the figure below 1Low pressure twinning kit d ID22 2 7 ...

Page 4: ...ver 2High pressure twinning pipe Insulation cover Heat resistant insulation material field supplied Tape field supplied Insulation covers can shrink Overlap the tape as shown in the left figure so that there will be no gap in between the insulation cover or field installed insulation material Overlap margin of the tape 5 Installing the water stopper Make sure to install the supplied water stopper ...

Reviews: