VI
Control ]
- 47 -
HWE09070
GB
(2) Outdoor unit (cooling only, heating only, cooling main and heating main modes)
Start
Breaker
turned on
Operation
command
Error stop
Error display on
the outdoor unit LED
Self-holding of
protection function
Operation command
to the WCB
Operation
mode
Error mode
52C1 ON
*Note 1
*Note 2
*Note 3
*Note 4
YES
YES
YES
YES
NO
NO
NO
fan
NO
"HO" / "PLEASE WAIT" blinks
on the remote controller
Operation command to the WCB
Cooling only, Heating only
Mixture of units in cooling and heating
Mixture of units in cooling and heating
Protection function
self-holding cancelled.
Normal operation
1. 52C1 4-way valve OFF
2. Inverter output 0Hz
3. Fan stop
4. All solenoid valves OFF
Cooling Only
Heating Only
2
2
Cooling Main
Operation
mode
Operation
mode
*Note 1. For about three minutes after power on, a search for the outdoor unit address, WCB address, indoor unit
address, remote controller address, and group information will start. During the search,
"HO"/ "PLEASE WAIT" blinks on the display of the remote controller. When the indoor unit to be controlled
by the remote controller is missing, "HO"/ "PLEASE WAIT" keeps blinking on the display of the remote
controller, even after three or more minutes have passed after power on.
*Note 3. The units will follow the operation mode commands from WCB.
*Note 4. When the operation mode commands from WCB are mixed (both cooling and heating), the actual operation mode
(Cooling-main or Heating-main) is determined by the outdoor unit.
*Note 2. The system may go into the error mode on the indoor unit, WCB, or outdoor unit side. The outdoor units will stop
only when all of the connected indoor units are experiencing a problem. If at least one of the indoor units is in
normal operation, the outdoor unit will continue in operation, displaying an error code on the LED.
Heating Main
Indoor units
registered to the
remote controller
Error
Unit in the stopped state
Summary of Contents for CMB-PW202V-J
Page 1: ...Service Handbook AIR CONDITIONERS MODEL CMB PW202V J ...
Page 9: ...HWE09070 GB ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 28: ... II Restrictions 19 HWE09070 GB ...
Page 31: ... 22 II Restrictions GB HWE09070 ...
Page 37: ... 28 ...
Page 40: ... III WCB Components 31 HWE09070 GB 3 WCB Circuit Board SW1 SW2 SW5 SW6 SW4 ...
Page 41: ... 32 III WCB Components GB HWE09070 ...
Page 42: ... 33 HWE09070 GB IV Electrical Wiring Diagram 1 Electrical Wiring Diagram of the WCB 35 ...
Page 43: ... 34 ...
Page 45: ... 36 IV Electrical Wiring Diagram GB HWE09070 ...
Page 47: ... 38 ...
Page 51: ... 42 ...
Page 61: ... 52 VI Control GB HWE09070 ...
Page 63: ... 54 ...
Page 73: ... 64 ...
Page 109: ... 100 ...