II
Restrictions ]
- 23 -
HWE09070
GB
[4] Restrictions on Pipe Length
1) All the indoor units that are connected to the same ports can only be operated in the same operation mode (cooling/heating).
2) Joint branching is not possible after header branching.
3) Cover the unused branch using the optional cover cap (CMY-S202-J).
4) Top-bottom differential 90m [295ft] (OU above IU) or 60m [196ft] (OU below IU) is not available.
C
L2
(Line branch possible)
d
Indoor
e
Indoor
f
Indoor
g
PWFY
PWFY
PWFY
PWFY
H
H’
h1
h2
A
B
Outdoor unit
WCB
Header branch
D
E
L1
PWFY branch
Line branch
(Header branch
possible)
Indoor/PWFY
branch
b
c
a
capped
Unit: m [ft]
Operation
Pipe sections
Allowable length of pipes
Length
Total pipe length
A+B+C+D+E+a+b+c+d
+e+f+g
Refer to the restrictions on the total piping
length in the graph on the next page.
Total pipe length from the outdoor unit
to the farthest indoor unit
A+C+D+E+g / A+B+c
165 [541] or less
(Equivalent length 190 [623] or less)
Between outdoor unit and WCB
A
110 [360] or less
Between WCB and indoor unit
C+D+E+g / B+c
40 [131] or less
*1
Height
difference Between indoor
and outdoor units
Outdoor unit
above indoor unit
H
50 [164] or less
Outdoor unit be-
low indoor unit
H'
40 [131] or less
Between indoor unit and WCB
h1
15 [49] (10[32]) or less
*2
Between indoor units
h2
15 [49] (10[32]) or less
*2
*1. When the overall pipe length between the WCB and the farthest indoor unit exceeds 40m [131ft], observe the restric-
tions in the figure titled "Restrictions on pipe length" below. (Except the P250 models)
*2. When the capacity of the connected indoor units is P200 or above, use the figures in the parentheses as a reference.
Summary of Contents for CMB-PW202V-J
Page 1: ...Service Handbook AIR CONDITIONERS MODEL CMB PW202V J ...
Page 9: ...HWE09070 GB ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 28: ... II Restrictions 19 HWE09070 GB ...
Page 31: ... 22 II Restrictions GB HWE09070 ...
Page 37: ... 28 ...
Page 40: ... III WCB Components 31 HWE09070 GB 3 WCB Circuit Board SW1 SW2 SW5 SW6 SW4 ...
Page 41: ... 32 III WCB Components GB HWE09070 ...
Page 42: ... 33 HWE09070 GB IV Electrical Wiring Diagram 1 Electrical Wiring Diagram of the WCB 35 ...
Page 43: ... 34 ...
Page 45: ... 36 IV Electrical Wiring Diagram GB HWE09070 ...
Page 47: ... 38 ...
Page 51: ... 42 ...
Page 61: ... 52 VI Control GB HWE09070 ...
Page 63: ... 54 ...
Page 73: ... 64 ...
Page 109: ... 100 ...