13.4. Changing blower external static pressure
The air handler is equipped with an adjustable static pressure
setting. The available settings are shown in the table below.
Model
Available ESP [in. WG]
PVFYP08
0.30
0.50
0.80
PVFYP12
0.30
0.50
0.80
PVFYP18
0.30
0.50
0.80
PVFYP24
0.30
0.50
0.80
PVFYP30
0.30
0.50
0.80
PVFYP36
0.30
0.50
0.80*
PVFYP42
0.30
0.50
0.80
PVFYP48
0.30
0.50
0.80
PVFYP54
0.30
0.50
0.80**
*PVFY-P36 in Downflow External Static pressure: 0.60
**PVFY-P54 in Downflow External Static pressure: 0.70
The air handler will be set to 0.50 ESP from the factory.
The blower static pressure setting can be changed by changing the
dip switches SWA & SWC. Vertical, Horizontal Right, and Horizontal
Left Switch C will always be in the “1” position. When the air handler
is installed in the Downflow position, Switch C needs to be in the “2”.
position.
External Static Pressure
Switch A
0.3 in. WG
(75 Pa)
0.5 in. WG
(125 Pa)
(
Factory Setting)
0.8 in. WG
(200 Pa)
Switch C
Switch C
Vertical,
Horizontal Right,
Horizontal Left
(
Factory Setting)
Downflow
Locate the CN31 connector in the upper right-hand corner of the
circuit board. Carefully remove the connector with the jumper from
the board. Cut the jumper on the CN31 connector and wire a
normally closed safety float switch across these wires.
Carefully reinstall the connector back onto the board
Upper right corner
of circuit board
CN31
Normally Closed
Float switch
SWA
SWA
SWA
1
2
3
1
2
3
1
2
3
2
1
1
2
2
1
1
2
External Static Pressure
Switch A
0.3 in. WG
(75 Pa)
0.5 in. WG
(125 Pa)
(
Factory Setting)
0.8 in. WG
(200 Pa)
Switch C
Switch C
Vertical,
Horizontal Right,
Horizontal Left
(
Factory Setting)
Downflow
Locate the CN31 connector in the upper right-hand corner of the
circuit board. Carefully remove the connector with the jumper from
the board. Cut the jumper on the CN31 connector and wire a
normally closed safety float switch across these wires.
Carefully reinstall the connector back onto the board
Upper right corner
of circuit board
CN31
Normally Closed
Float switch
SWA
SWA
SWA
1
2
3
1
2
3
1
2
3
2
1
1
2
2
1
1
2