background image

10

GB

D

F

I

NL

E

P

GR

RU

TR

Restriction

• If a flammable gas or air (oxygen) is used as the pressurization

gas, it may catch fire or explode.

• Do not use a refrigerant other than that indicated on the unit.

• Sealing with gas from a cylinder will cause the composition of

the refrigerant in the cylinder to change. (For R407C models)

• Use a pressure gauge, charge box, and other parts especially for

R407C. (For R407C models)

• An electric leak detector for R22 cannot detect leaks of R407C.

• Do not use a haloid torch. (Leaks cannot be detected.)

Airtight test procedure

1. Nitrogen gas pressurization

(1) After pressurizing to the design pressure (2.94 MPa) using nitrogen gas, let stand for about

one day. If the pressure does not drop, airtightness is good.

However, if the pressure drops, since the leaking point is unknown, the following bubble test

may also be performed.

(2) After the pressurization described above, spray the flare connection parts, brazed parts, flanges,

and other parts that may leak with a bubbling agent (Kyuboflex, etc.) and visually check for bubbles.

(3) After the airtight test, wipe off the bubbling agent.

2. Pressurization using refrigerant gas and nitrogen gas

(1) Pressurizing to a gas pressure of approximately 0.2 MPa, pressurize to the design pressure

(2.94 MPa) using nitrogen gas.

However, do not pressurize at one time. Stop during pressurization and check that the pres-

sure does not drop.

(2) Check for gas leaks by checking the flare connection parts, brazed parts, flanges, and other

parts which may leak using an R407C compatible electric leak detector.

(3) This test may be used together the with bubble type gas leak test.

2

Evacuation

Evacuate with the ball valve of the outdoor unit closed and evacuate both the
connection piping and the indoor unit from the service port provided on the ball
valve of the outdoor unit using a vacuum pump. (Always evacuate from the
service port of both the high press pipe and the low press pipe.) After the
vacuum reaches 650 Pa [abs], continue evacuation for at least one hour or
more.
* Never perform air purging using refrigerant.

[Fig. 8.3.2] (P.3)

A

System analyzer

B

Lo Knob

C

Hi Knob

D

Ball valve

E

Low press pipe

F

High press pipe

G

Service port

H

Three-way joint

I

Valve

J

Valve

K

Cylinder

L

Scale

M

Vacuum pump

Note:

Always add an appropriate amount of refrigerant. Also always seal the
system with liquid refrigerant. Too much or too little refrigerant will cause
trouble.

[Fig. 8.2.2] (P.3)

<A> [Ball valve (low press side)]

(This figure shows the valve in the fully open state.)

<B> [Ball valve (high press side)]

A

Valve stem
[Fully closed at the factory, when connecting the piping, when evacuating, and
when charging additional refrigerant. Open fully after the operations above are
completed.]

B

Stopper pin [Prevents the valve stem from turning 90

°

 or more.]

C

Packing (Accessory)
[Manufacturer: Nichiasu corporation]
[Type: T/#1991-NF]

D

Connecting pipe (Accessory)
[Use packing and securely install this pipe to the valve flange so that gas leakage
will not occur. (Tightening torque: low press side 43 N·m (430 kg·cm), high press
side 25 N·m (250 kg·cm)) Coat both surfaces of the packing with refrigerator oil
(Ester oil, ether oil or alkylbenzene [small amount]).]

E

Open (Operate slowly)

F

Cap, copper packing
[Remove the cap and operate the valve stem. Always reinstall the cap after opera-
tion is completed. (Valve stem cap tightening torque: 25 N·m (250 kg·cm) or more)]

G

Service port
[Use this port to evacuate the refrigerant piping and add an additional charge at
the site.
Open and close the port using a double-ended wrench.
Always reinstall the cap after operation is completed. (Service port cap tightening
torque: 14 N·m (140 kg·cm) or more)]

H

ø25.4

I

ø34.93

J

Field piping
[Braze to the connecting pipe. (When brazing, use unoxidized brazing.)]

K

Close-packed packing

L

Hollow packing

Appropriate tightening torque by torque wrench:

Copper pipe external dia. (mm)

Tightening torque (N·m) / (kg·cm)

ø6.35

14 to 18 / 140 to 180

ø9.52

35 to 42 / 350 to 420

ø12.7

50 to 57.5 / 500 to 575

ø15.88

75 to 80 / 750 to 800

ø19.05

100 to 140 / 1000 to 1400

Tightening angle standard:

Pipe diameter (mm)

Tightening angle (

°

)

ø6.35, ø9.52

60 to 90

ø12.7, ø15.88

30 to 60

ø19.05

20 to 35

[Fig. 8.2.3] (P.3)

Note:
If a torque wrench is not available, use the following method as a standard:
When you tighten the flare nut with a wrench, you will reach a point where
the tightening torque will abruptly increase. Turn the flare nut beyond this
point by the angle shown in the table above.

 Caution:

Always remove the connecting pipe from the ball valve and braze it out-
side the unit.

- Brazing the connecting pipe while it is installed will heat the ball valve and

cause trouble or gas leakage. The piping, etc. inside the unit may also be
burned.

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections. (For R407C models)

- The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.

8.3. Airtight test, evacuation, and refrigerant

charging

1

Airtight test

Perform with the stop valve of the outdoor unit closed, and pressurize the con-
nection piping and the indoor unit from the service port provided on the stop
valve of the outdoor unit. (Always pressurize from both the high press pipe and
the low press pipe service ports.)

[Fig. 8.3.1] (P.3)

A

Nitrogen gas

B

To indoor unit

C

System analyzer

D

Lo Knob

E

Hi Knob

F

Stop valve

G

Low press pipe

H

High press pipe

I

Outdoor unit

J

Service port

<For R407C models>
The method of conducting the airtight test is basically the same as for R22 models.
However, since the restrictions have a large affect on deterioration of the refrigera-
tor oil, always observe them. Also, with nonazeotropic refrigerant (R407C, etc.),
gas leakage causes the composition to change and affects performance. There-
fore, perform the airtightness test cautiously.

Use a gauge manifold, charging hose, and other parts for the refrigerant
indicated on the unit.

Use a graviometer. (One that can measure down to 0.1 kg.)

Use a vacuum pump with a reverse flow check valve. (For R407C models)
(Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum
Gauge)
Also use a vacuum gauge that reaches 0.5 Torr or greater after operating
for five minutes.

3

Refrigerant Charging (For R407C models)

Since the refrigerant used with the unit is nonazerotropic, it must be charged in the
liquid state. Consequently, when charging the unit with refrigerant from a cylinder,
if the cylinder does not have a syphon pipe, charge the liquid refrigerant by turning
the cylinder upside-down as shown below. If the cylinder has a syphon pipe like
that shown in the figure at the right, the liquid refrigerant can be charged with the
cylinder standing upright. Therefore, give careful attention to the cylinder specifica-
tions. If the unit should be charged with gas refrigerant, replace all the refrigerant
with new refrigerant. Do not use the refrigerant remaining in the cylinder.

[Fig. 8.3.3] (P.3)

Summary of Contents for CITY MULTI PURY-P400YMF-C

Page 1: ...leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XE...

Page 2: ...10 56 56 A D 150 Ø62 Ø27 230 111 B A Fig 6 1 2 A Top view B Side view C When there is little space up to an obstruction A Front B No restrictions on wall height left and right C Air outlet guide Procured at the site A Knock out hole B Bottom piping C Front piping A M10 anchor bolt procured at the site B Corner is not seated A Bottom piping through hole B bolt hole C bolt hole for old models D Bott...

Page 3: ...sory D Connecting pipe Accessory E Open Operate slowly F Cap copper packing G Service port H ø25 4 I ø34 93 J Field piping K Close packed packing L Hollow packing A System analyzer B Lo Knob C Hi Knob D Ball valve E Low press pipe F High press pipe G Service port H Three way joint I Valve J Valve K Cylinder L Scale M Vacuum pump A Nitrogen gas B To indoor unit C System analyzer D Lo Knob E Hi Knob...

Page 4: ...IC 51 M1M2S TB5 RC 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 101 RC 105 RC 104 RC 155 OC M1M2 M1M2S TB7 TB3 53 OC r3 BC M1M2S 52 BS M1M2S 55 BC M1M2S 54 M1M2S Power Supply Unit M1M2S MJ103 L3 L 6 L 7 L4 L 5 r 2 r 4 r 1 A B A B A B A B A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer coverin...

Page 5: ...Fig 9 4 1 E E D A E E A B C C 3 N 380 450 V 220 240 V L N PE L1 L2 L3 N PE A Switch Breakers for Wiring and Current Leakage B Outdoor Unit C BC Controller master C BC Controller slave D Pull Box E Indoor Unit ...

Page 6: ... the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the re...

Page 7: ...t may cause the refrigerator oil to deteriorate Use a vacuum pump with a reverse flow check valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base refrigerant recovery equ...

Page 8: ...ving particles oils moisture or any other contaminant For R407C models 2 Commercially available piping often contains dust and other materials Always blow it clean with a dry inert gas 3 Use care to prevent dust water or other contaminants from entering the piping during installation 4 Reduce the number of bending portions as much as possible and make bend ing radius as big as possible 5 Always ob...

Page 9: ...ge hose gas leak detector check valve refriger ant charge base vacuum gauge refrigerant recovery equipment Mixing of conventional refrigerant and refrigerator oil may cause the refrig erator oil to deteriorate Mixing of water will cause the refrigerator oil to deteriorate R407C refrigerant does not contain any chlorine Therefore gas leak detec tors for conventional refrigerants will not react to i...

Page 10: ...m 250 kg cm or more G Service port Use this port to evacuate the refrigerant piping and add an additional charge at the site Open and close the port using a double ended wrench Always reinstall the cap after operation is completed Service port cap tightening torque 14 N m 140 kg cm or more H ø25 4 I ø34 93 J Field piping Braze to the connecting pipe When brazing use unoxidized brazing K Close pack...

Page 11: ...ng for control hereinafter referred to as transmission line shall be 5 cm or more apart from power source wiring so that it is not influenced by electric noise from power source wiring Do not insert transmission line and power source wire in the same conduit 3 Be sure to provide designated grounding work to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor ...

Page 12: ...its and the total number of remote controllers is displayed within the parenthesis 1 If even one unit that is higher than 200 exists in the cooling system the maximum capacity will be 200 or higher Branch Setting Set the indoor unit branch No switch to the branch No of the BC controller connecting the piping and that indoor unit When using two or more branches set the lowest branch No The indoor u...

Page 13: ... to the same branch of the BC controller the heating cooling operation cannot be performed while another indoor unit is performing a cooling heating operation Because of the control operation of auto vane it may change over to horizontal blow automatically from the downward blow in cooling in case the downward blow operation has been continued for 1 hour At defrosting in heating hot adjust ing and...

Page 14: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Page 15: ...mber PURY P500YMF C PURY P400 500YMF C_Service_Manual_ MDOC PURY P400 500YMF C_Declaration_of_Conformity PURY P400 500YMF C_Installation_Manual_ WT03692X01 PURY P400 500YMF C_Parts_Catalog_ BWE02030 PURY YMF C_DataBook_2002 ...

Reviews: