1. Safety precautions

1.1. Before installation and electric work

s

Before installing the unit, make sure you read all the “Safety
precautions”.

s

The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury
or death to the user.

 Caution:

Describes precautions that should be observed to prevent damage to the
unit.

Symbols used in the illustrations

: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Beware of electric shock. (This symbol is displayed on the main unit label.)

<Color: yellow>

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

Ask the dealer or an authorized technician to install the air conditioner.

- Improper installation by the user may result in water leakage, electric shock,

or fire.

Install the unit at a place that can withstand its weight.

- Inadequate strength may cause the unit to fall down, resulting in injuries.

Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.

- Inadequate connection and fastening may generate heat and cause a fire.

Prepare for strong winds and earthquakes and install the unit at the speci-
fied place.

- Improper installation may cause the unit to topple and result in injury.

Always use an filter and other accessories specified by Mitsubishi Elec-
tric.

- Ask an authorized technician to install the accessories. Improper installation

by the user may result in water leakage, electric shock, or fire.

Never repair the unit. If the air conditioner must be repaired, consult the
dealer.

- If the unit is repaired improperly, water leakage, electric shock, or fire may

result.

Do not touch the heat exchanger fins.

- Improper handling may result in injury.

If refrigerant gas leaks during installation work, ventilate the room.

- If the refrigerant gas comes into contact with a flame, poisonous gases will

be released.

Install the air conditioner according to this Installation Manual.

- If the unit is installed improperly, water leakage, electric shock, or fire may

result.

Have all electric work done by a licensed electrician according to “Elec-
tric Facility Engineering Standard” and “Interior Wire Regulations”and
the instructions given in this manual and always use a special circuit.

- If the power source capacity is inadequate or electric work is performed im-

properly, electric shock and fire may result.

Securely install the outdoor unit terminal cover (panel).

- If the terminal cover (panel) is not installed properly, dust or water may enter

the outdoor unit and fire or electric shock may result.

When installing and moving the air conditioner to another site, do not
charge it with a refrigerant different from the refrigerant (R407C) speci-
fied on the unit.

- If a different refrigerant or air is mixed with the original refrigerant, the refrig-

erant cycle may malfunction and the unit may be damaged.

If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant should leak.

- Consult the dealer regarding the appropriate measures to prevent the safety

limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.

When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.

- If the air conditioner is installed improperly, water leakage, electric shock, or

fire may result.

After completing installation work, make sure that refrigerant gas is not
leaking.

- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or

other heat source, it may generate noxious gases.

Do not reconstruct or change the settings of the protection devices.

- If the pressure switch, thermal switch, or other protection device is shorted

and operated forcibly, or parts other than those specified by Mitsubishi Elec-
tric are used, fire or explosion may result.

To dispose of this product, consult your dealer.

The installer and system specialist shall secure safety against leakage
according to local regulation or standards.

- Following standards may be applicable if local regulation are not available.

Pay a special attention to the place, such as a basement, etc. where re-
frigeration gas can not disperse into the atmosphere, since refrigeration
is heavier than the air.

1.2. Precautions for devices that use R407C

refrigerant

 Caution:

Do not use the existing refrigerant piping.

- The old refrigerant and refrigerator oil in the existing piping contains a large

amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.

Use refrigerant piping made of phosphorus deoxidized copper and cop-
per alloy seamless pipes and tubes. In addition, be sure that the inner
and outer surfaces of the pipes are clean and free of hazardous sulphur,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contami-
nant.

- Contaminants on the inside of the refrigerant piping may cause the refriger-

ant residual oil to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)

- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor trouble may result.

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.

- The refrigerator oil will degrade if it is mixed with a large amount of mineral

oil.

Use liquid refrigerant to fill the system.

- If gas refrigerant is used to seal the system,  the composition of the refriger-

ant in the cylinder will change and performance may drop.

1. Safety precautions ...................................................................................... 6

1.1. Before installation and electric work .......................................... 6
1.2. Precautions for devices that use R407C refrigerant .................. 6
1.3. Before getting installed .............................................................. 7
1.4. Before getting installed (moved) - electrical work ...................... 7
1.5. Before starting the test run ........................................................ 7

2. Specifications .............................................................................................. 7
3. Confirmation of parts attached ................................................................... 7
4. Space required around unit ........................................................................ 8
5. Lifting method and weight of product .......................................................... 8
6. Installation of unit ........................................................................................ 8

6.1. Installation ................................................................................. 8
6.2. Connecting direction for refrigerant piping ................................ 8

7. Refrigerant piping installation ..................................................................... 8

7.1. Caution ...................................................................................... 8
7.2. Refrigerant piping system .......................................................... 9

8. Additional Refrigerant Charge .................................................................... 9

8.1. Calculation of Additional Refrigerant Charge ............................ 9
8.2. Caution for piping connection/valve operation ........................... 9
8.3. Airtight test, evacuation, and refrigerant charging ................... 10
8.4. Thermal insulation of refrigerant piping ................................... 11

9. Wiring ........................................................................................................ 11

9.1. Caution .................................................................................... 11
9.2. Control box and connecting position of wiring ......................... 11
9.3. Wiring transmission cables ...................................................... 11
9.4. Wiring of main power supply and equipment capacity ............ 13

10. Test run ..................................................................................................... 13

10.1. The following phenomena do not represent trouble

(emergency) ............................................................................ 13

Summary of Contents for CITY MULTI PURY-P400YMF-C

Page 1: ...leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XE...

Page 2: ...10 56 56 A D 150 Ø62 Ø27 230 111 B A Fig 6 1 2 A Top view B Side view C When there is little space up to an obstruction A Front B No restrictions on wall height left and right C Air outlet guide Procured at the site A Knock out hole B Bottom piping C Front piping A M10 anchor bolt procured at the site B Corner is not seated A Bottom piping through hole B bolt hole C bolt hole for old models D Bott...

Page 3: ...sory D Connecting pipe Accessory E Open Operate slowly F Cap copper packing G Service port H ø25 4 I ø34 93 J Field piping K Close packed packing L Hollow packing A System analyzer B Lo Knob C Hi Knob D Ball valve E Low press pipe F High press pipe G Service port H Three way joint I Valve J Valve K Cylinder L Scale M Vacuum pump A Nitrogen gas B To indoor unit C System analyzer D Lo Knob E Hi Knob...

Page 4: ...IC 51 M1M2S TB5 RC 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 101 RC 105 RC 104 RC 155 OC M1M2 M1M2S TB7 TB3 53 OC r3 BC M1M2S 52 BS M1M2S 55 BC M1M2S 54 M1M2S Power Supply Unit M1M2S MJ103 L3 L 6 L 7 L4 L 5 r 2 r 4 r 1 A B A B A B A B A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer coverin...

Page 5: ...Fig 9 4 1 E E D A E E A B C C 3 N 380 450 V 220 240 V L N PE L1 L2 L3 N PE A Switch Breakers for Wiring and Current Leakage B Outdoor Unit C BC Controller master C BC Controller slave D Pull Box E Indoor Unit ...

Page 6: ... the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the re...

Page 7: ...t may cause the refrigerator oil to deteriorate Use a vacuum pump with a reverse flow check valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base refrigerant recovery equ...

Page 8: ...ving particles oils moisture or any other contaminant For R407C models 2 Commercially available piping often contains dust and other materials Always blow it clean with a dry inert gas 3 Use care to prevent dust water or other contaminants from entering the piping during installation 4 Reduce the number of bending portions as much as possible and make bend ing radius as big as possible 5 Always ob...

Page 9: ...ge hose gas leak detector check valve refriger ant charge base vacuum gauge refrigerant recovery equipment Mixing of conventional refrigerant and refrigerator oil may cause the refrig erator oil to deteriorate Mixing of water will cause the refrigerator oil to deteriorate R407C refrigerant does not contain any chlorine Therefore gas leak detec tors for conventional refrigerants will not react to i...

Page 10: ...m 250 kg cm or more G Service port Use this port to evacuate the refrigerant piping and add an additional charge at the site Open and close the port using a double ended wrench Always reinstall the cap after operation is completed Service port cap tightening torque 14 N m 140 kg cm or more H ø25 4 I ø34 93 J Field piping Braze to the connecting pipe When brazing use unoxidized brazing K Close pack...

Page 11: ...ng for control hereinafter referred to as transmission line shall be 5 cm or more apart from power source wiring so that it is not influenced by electric noise from power source wiring Do not insert transmission line and power source wire in the same conduit 3 Be sure to provide designated grounding work to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor ...

Page 12: ...its and the total number of remote controllers is displayed within the parenthesis 1 If even one unit that is higher than 200 exists in the cooling system the maximum capacity will be 200 or higher Branch Setting Set the indoor unit branch No switch to the branch No of the BC controller connecting the piping and that indoor unit When using two or more branches set the lowest branch No The indoor u...

Page 13: ... to the same branch of the BC controller the heating cooling operation cannot be performed while another indoor unit is performing a cooling heating operation Because of the control operation of auto vane it may change over to horizontal blow automatically from the downward blow in cooling in case the downward blow operation has been continued for 1 hour At defrosting in heating hot adjust ing and...

Page 14: ...e contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Page 15: ...mber PURY P500YMF C PURY P400 500YMF C_Service_Manual_ MDOC PURY P400 500YMF C_Declaration_of_Conformity PURY P400 500YMF C_Installation_Manual_ WT03692X01 PURY P400 500YMF C_Parts_Catalog_ BWE02030 PURY YMF C_DataBook_2002 ...

Reviews: