OCH791 _98
•
Low pressure sensor (63LS)
•
4-way valve (21S4)
•
Bypass valve (SV1)
Pull out the disconnected wires from the electrical parts box.
5. Remove the terminal cover and disconnect the compressor lead wire.
6. Remove 2 electrical parts box fixing screws (4 × 10) and detach the electrical parts box by pulling it upward.
The electrical parts box is fixed with 2 hooks on the left and 1 hook on the right.
Photo 4
Electrical
parts box
Noise filter
circuit board
(NF)
Terminal cover
Cover panel
(Front)
Cover panel
fixing screws
Compressor
(MC)
Valve bed
Multi controller
board (MULTI.B)
Front panel fixing
screws (5x12)
Front panel
fixing screws
(4x10)
Front panel
fixing screws (5x12)
Valve bed
fixing screws
Cover panel
(Rear)
Photo 5
Terminal block
(TB3) (TB7)
Electrical parts box
Electrical
parts box
fixing screws
Terminal block
(TB1)
Terminal block
(TB1B)
Hook
Hooks
4. Removing the thermistor <Suction pipe> (TH6)
1. Remove the service panel. (See Photo 1)
2. Remove the top panel. (See Photo 1)
3. Disconnect the connectors TH6 and TH7 (red) on the outdoor multi controller circuit board in the electrical parts box.
4. Loosen the wire clamps on the side of the electrical parts box.
5. Pull out the thermistor <Suction pipe> (TH6) from the sensor holder.
Note:
•
When replacing thermistor <Suction pipe> (TH6), replace it together with thermistor <Ambient> (TH7) since they are
combined together. Refer to procedure No.5 to remove thermistor <Ambient> (TH7).
Photo 6
Electrical parts box
Clamps
Photo 7
Thermistor
<Suction pipe> (TH6)
Thermistor
<Compressor>
(TH4)
Thermistor
<HIC pipe>
(TH2)
Compressor
(MC)
Ball valve
fixing screws
Stop valve fixing screws
5. Removing the thermistor <Ambient> (TH7)
1. Remove the service panel. (See Photo 1)
2. Remove the top panel. (See Photo 1)
3. Disconnect the connector TH7 (red) on the outdoor multi controller circuit board in the electrical parts box.