OCH791 _23
8-1-3. Countermeasures for error during test run
If a problem occurs during test run, a code number will appear on the remote controller (or LED on the outdoor unit), and
the air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Error
code
(2 digits)
Error
code
(4 digits)
Trouble
Detected Unit
Remarks
Indoor
Outdoor Remote
Controller
Ed
0403 Serial communication error/Model selection SW error
О
Outdoor unit outdoor multi controller circuit
board
– Power circuit board communication trouble
Incorrect setting of model selection
U2
1102 Compressor temperature trouble
О
Check delay code 1202
UE
1302 High pressure trouble
О
Check delay code 1402
U7
1500 Superheat due to low discharge temperature trouble
О
Check delay code 1600
U2
1501 Refrigerant shortage trouble
О
Check delay code 1601
Closed valve in cooling mode
О
Check delay code 1501
P6
1503 Freeze protection of plate heat exchanger
О
Freeze protection of branch box or indoor unit
О
EF
1508
4-way valve trouble in heating mode
О
Check delay code 1608
L6
2135 Circulation water freeze protection
О
PA
2500 Water leakage
О
P5
2502
Drain overflow protection
О
P4
2503 Drain sensor abnormality
О
UF
4100 Compressor current interruption (locked compressor)
О
Check delay code 4350
Pb
4114 Fan trouble (Indoor unit)
О
UP
4210 Compressor overcurrent interruption
О
U9
4220 Voltage shortage/overvoltage/PAM error/L1 open
phase/primary current sensor error/power synchroni
-
zation signal error
О
Check delay code 4320
U5
4230 Heat sink temperature trouble
О
Check delay code 4330
U6
4250 Power module trouble
О
Check delay code 4350
U8
4400 Fan trouble (Outdoor unit)
О
Check delay code 4500
U3
5101 Air inlet thermistor (TH21) open/short
О
Compressor temperature thermistor (TH4) open/short
О
Check delay code 1202
U4
5102 Liquid pipe temperature thermistor (TH22) open/short
О
Suction pipe temperature thermistor (TH6) open/short
О
Check delay code 1211
U4
5103 Gas pipe temperature thermistor (TH23) open/short
О
U4
5105 Outdoor liquid pipe temperature thermistor (TH3)
open/short
О
Check delay code 1205
U4
5106 Ambient temperature thermistor (TH7) open/short
О
Check delay code 1221
U4
5109 HIC pipe temperature thermistor (TH2) open/short
О
Check delay code 1222
U4
5110 Heat sink temperature thermistor (TH8) open/short
О
Check delay code 1214
F5
5201 High pressure sensor (63HS) trouble
О
Check delay code 1402
F3
5202 Low pressure sensor (63LS) trouble
О
Check delay code 1400
UH
5300 Primary current error
О
Check delay code 4310
P4
5701
Contact failure of drain float switch
О
A0
6600 Duplex address error
О
О
О
Only M-NET Remote controller is detected.
A2
6602 Transmission processor hardware error
О
О
О
Only M-NET Remote controller is detected.
A3
6603 Transmission bus BUSY error
О
О
О
Only M-NET Remote controller is detected.
A6
6606 Signal communication error with transmission proces
-
sor
О
О
О
Only M-NET Remote controller is detected.
A7
6607 No ACK error
О
О
Only M-NET Remote controller is detected.
A8
6608 No response frame error
О
О
Only M-NET Remote controller is detected.
E0/E4
6831 MA communication receive error
О
О
Only MA Remote controller is detected.
E3/E5
6832 MA communication send error
О
О
Only MA Remote controller is detected.
E3/E5
6833 MA communication send error
О
О
Only MA Remote controller is detected.
E0/E4
6834 MA communication receive error
О
О
Only MA Remote controller is detected.
EF
7100 Total capacity error
О
EF
7101 Capacity code error
О
О
EF
7102 Connecting excessive number of units and branch
boxes
О
EF
7105 Address setting error
О
EF
7130 Incompatible unit combination
О
Notes:
• When the outdoor unit detects No ACK error/No response error, the target indoor unit is treated as a stop, and not assumed to be abnormal.
•
The error codes displayed on the units may be different between the error source and others. In that case, please refer to the error code of error source
by displayed attribute and address.
• Refer to the service manual of indoor unit or remote controller for the detail of error detected in indoor unit or remote controller.
■
Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LED1, LED2 (LED
indication) found on the multi-controller of the outdoor unit.
LED indication: Set all contacts of SW1 to OFF.
■
During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Bit
1
2
3
4
5
6
7
8
Indication
Compressor
operated
52C
21S4
SV1
(SV2)
—
—
Always lit
• Example
When the compressor and SV1 are on during cooling operation.
1 2 3 4 5 6 7 8