–58–
4)
Deletion of information on address not existing
• Deletion of information on address not existing .................
5
This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by
the miss setting at test run, or due to the old memory remained at the alteration/modification of group composition,
and the address not existing will be deleted.
Note : The connection information (connection between indoor unit and outdoor unit) on the refrigerant system can
not be deleted.
An example to delete the system controller of “250” from the indoor unit of “007” is shown below.
[Operation procedure]
1
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
switch (
A
+
B
) at the same time for 2 seconds to change to the registration mode.
2
Operate
switch (
G
) for the interlocked setting mode ( ii ). (See the figure below.)
3
Assign the unit address existing to “OA UNIT ADDRESS No.” with the
(Room temperature control) switch (
C
),
and press
switch (
E
) to call the address to be deleted. (See the figure below.) As the error display on the remote
controller is usually transmitted from the indoor unit, “OA UNIT ADDRESS No.” is used as the address of the indoor unit.
4
Press the
CLOCK
ON
OFF
switch (
F
) twice. (See the figure below.)
5
After completing the deletion, continuously press the
FILTER
+
switch (
A
+
B
) at the same time for 2 seconds
to return to the original ordinary mode (with the remote controller under stopping).
INDOOR UNIT
ADDRESS NO
ERROR CODE
OA UNIT ADDRESS NO
˚C
INDOOR UNIT
ADDRESS NO
ERROR CODE
OA UNIT ADDRESS NO
˚C
(Alternative
display)
INDOOR UNIT
ADDRESS NO
ERROR CODE
OA UNIT ADDRESS NO
˚C
INDOOR UNIT
ADDRESS NO
ERROR CODE
OA UNIT ADDRESS NO
˚C
(Alternative
display)
ON/OFF –
STAND BY
DEFROST
INDOOR UNIT
ADDRESS NO.
ERROR CODE
OA UNIT ADDRESS NO.
CENTRALLY CONTROLLED
CLOCK
ON
OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
TEST RUN
ON
OFF
CLOCK
FILTER
CHECK
TEST RUN
REMOTE CONTROLLER
NETWORK
PAR-F25MA
TEMP.
TIMER SET
INDOOR UNIT
ADDRESS NO
ERROR CODE
OA UNIT ADDRESS NO
˚C
INDOOR UNIT
ADDRESS NO
ERROR CODE
OA UNIT ADDRESS NO
˚C
(Alternative
display)
▲
▲
▼
When both indoor
unit and interlocked
unit addresses are
existing
Deletion of
address not
existing
1
Set the address (
H
)
3
Press the deletion switch (
F
) twice
• Deletion completed
• Deletion completed
1
+
2
3
3
2
Press the switch for
confirmation (
E
)
Summary of Contents for CITY MULTI PUHY-400YMF-B
Page 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Page 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Page 26: ... 23 ...
Page 50: ... 47 ...
Page 152: ... 149 Model PUHY 400YMF B 500YMF B ...